beautypg.com

Technical data 81, Environmental conditions 81, Power supply 81 – West Control Solutions N8840 User Manual

Page 81: Safety test 81, Technical data

background image

POWER SUPPLY

Dependent of order:

AC SUPPLY

Voltage:

90...260 V AC

Frequency:

48...62 Hz

Power consumption approx. 7,0 VA

UNIVERSAL SUPPLY 24 V UC

AC voltage:

20,4...26,4 V AC

Frequency:

48...62 Hz

DC voltage:

18...31 V DC

Power consumption:

approx.. 7,0 VA

BEHAVIOUR WITH POWER FAILURE

Configuration, parameters and adjusted

set-points, control mode:
Non-volatile storage in EEPROM

FRONT INTERFACE

Connection of PC via PC adapter (see

"Accessory equipment"). The 8800/8840

Configurator software is used to configure, set

parameters and operate the 8840 profiler.

BUS INTERFACE (OPTION)

Galvanically isolated

Physical:

RS 422/485

Protocol:

Modbus RTU

Transmission speed: 2400, 4800, 9600, 19.200

bits/sec

Address range:

1...247

Number of controllers per bus: 32

Repeaters must be used to connect a higher number

of controllers.

ENVIRONMENTAL CONDITIONS

Protection modes

Front panel:

IP 65 (NEMA 4X)

Housing:

IP 20

Terminals:

IP 00

Permissible temperatures

For specified

accuracy:

0...60°C

Warm-up time:

≥ 15 minutes

For operation:

-20...65°C

For storage:

-40...70°C

Humidity

75% yearly average, no condensation

Shock and vibration

Vibration test Fc (DIN 68-2-6)

Frequency:

10...150 Hz

Unit in operation:

1g or 0,075 mm

Unit not in operation: 2g or 0,15 mm

Shock test Ea (DIN IEC 68-2-27)

Shock:

15g

Duration:

11ms

Electromagnetic compatibility

Complies with EN 61 326-1

(for continuous, non-attended operation)

GENERAL

Housing

Material:

Makrolon 9415

flame-retardant

Flammability class:

UL 94 VO, self-extinguishing

Plug-in module, inserted from the front

Safety test

Complies with EN 61010-1 (VDE 0411-1):

Overvoltage category II

Contamination class 2

Working voltage range 300 V

Protection class II

Technical data

8840 profiler

81