4.6.8 Continuous controller with integrated positioner ( Cntr/ C.Fnc = 6 )
This is basically a cascade. A tracking controller with three-point stepping
behaviour which operates with Yp as process value (INP.2 / INP.3) is used with
the continuous controller.
ConF / Cntr
SP.Fn = 0
Setpoint controller
C.Fnc = 6
Continuous controller with
integrated positioner
C.Act = 0
Direction of operation invers
(e.g. heating)
ConF / InP.2: I.Fnc = 3
Position featback Yp
S.typ = 50
Sensor e.g. potentiometer 0..160 Ω
ConF / Out.1: O.Act = 0
Direction of operation Out.1 direct
Y.1
= 1
Controller output Y1 activ
Y.2
= 0
Controller output Y2 not activ
ConF / Out.2: O.Act = 0
Direction of operation Out.2 direct
Y.1
= 0
Controller output Y1 not activ
Y.2
= 1
Controller output Y2 activ
PArA / Cntr: Pb1
= 0,1...9999
Proportional band 1 (heating)
in phys. units (e.g. °C)
ti1
= 1...9999
Integral action time 1 (heating)
in sec.
td1
= 1...9999
Derivative action time t 1 (heating)
in sec.
t1
= 0,4...9999
Minimal cycle time 1 (heating)
SH
= 0...9999
Neutral zone in phys. units (e.g.°C)
Configuration level
Configuration examples
56
8840 profiler
W
X
M
OUT.4
OUT.1
OUT.2
INP.2
Ypid
Position controller
INP.1
Y.1
Y.2
Master controller
Ycontinuous
X
W
SP