West Control Solutions N8840 User Manual
Page 36
Configuration level
Configuration parameters
36
8840 profiler
Name
Value range Description
Default
Src.2
Source of limit 2
0
0
process value
1
control deviation xw (process value - set-point)
2
control deviation xw (with suppression after start-up and
set-point change)
After switch-on or set-point changing, the alarm output is
suppressed, until the process value is within the limits for the
first time. At the latest after elapse of time 10 ti1the alarm is
activated (ti1 = integral time 1; parameter r Cntr)
If ti1 is switched off (ti1 = 0), this is interpreted as Î ,
i.e. the alarm is not activated, before the process value was
within the limits once.
3
measured value INP1
4
measured value INP2
5
measured value INP3
6
effective setpoint Weff
7
correcting variable y (controller output)
8
control variable deviation xw (actual value - internal setpoint)
= deviation alarm to internal setpoint
9
difference x1 - x2 (utilizable e.g. in combination with process
value function “mean value” for recognizing aged
thermocouples
Fnc.3
Function of limit 3
0
0
switched off
1
measured value monitoring
2
Measured value monitoring + alarm status storage. A stored
limit value can be reset via error list,
è
-key, Ò-key or a
digital input ( -> LOGI/ Err.r)
3
signal change (change/minute)
4
signal change and storage (change/minute)
Src.3
Source of limit 3
0
0
process value
1
control deviation xw (process value - set-point)
2
control deviation xw (with suppression after start-up and
set-point change)
After switch-on or set-point changing, the alarm output is
suppressed, until the process value is within the limits for the
first time. At the latest after elapse of time 10 ti1 the alarm
is activated (ti1 = integral time 1; parameter r Cntr)
If ti1 is switched off (ti1 = 0), this is interpreted as Î ,
i.e. the alarm is not activated, before the process value was
within the limits once.
3
measured value INP1
4
measured value INP2
5
measured value INP3
6
effective setpoint Weff
7
correcting variable y (controller output)
8
control variable deviation xw (actual value - internal setpoint)
= deviation alarm to internal setpoint
9
difference x1 - x2 (utilizable e.g. in combination with process
value function “mean value” for recognizing aged
thermocouples