Othr – West Control Solutions N8840 User Manual
Page 43

Configuration level
8840 profiler
43
Configuration parameters
Name
Value range Description
Default
fDI3
Forcing di3 (only visible with 8800/8840 Configurator!)
0
0
No forcing
1
Forcing via serial interface
othr
Name
Value range Description
Default
bAud
Baudrate of the interface (only visible with OPTION)
2
0
2400 Baud
1
4800 Baud
2
9600 Baud
3
19200 Baud
Addr
1...247
Address on the interace (only visible with OPTION)
1
PrtY
Data parity on the interface (only visible with OPTION)
1
0
no parity (2 stop bits)
1
even parity
2
odd parity
3
no parity (1 stopbit)
dELY
0...200
Delay of response signal [ms] (only visible with OPTION)
0
Unit
Unit
1
0
without unit
1
°C
2
°F
dP
Decimal point (max. number of digits behind the decimal
point)
0
0
no digit behind the decimal point
1
1 digit behind the decimal point
2
2 digits behind the decimal point
3
3 digits behind the decimal point
LED
Function allocation of status LEDs 1 / 2 / 3 / 4
0
10
OUT1, OUT2, OUT3, OUT4
11
Heating, alarm 1, alarm 2, alarm 3
12
Heating, cooling, alarm 1, alarm 2
13
Cooling, heating, alarm 1, alarm 2
14
Bus error
20
Y1, Y2, track1, track2
21
Y2, Y1, track1, track2
22
track1, track2, track3, track4
dISP
0...10
Display luminosity
5
C.dEl
0..200
Modem delay [ms]
Additional delay time, before the received message is
evaluated in the Modbus. This time is required, unless
messages are transferred continuously during modem
transmission.
0
dP.AD
0...126
Profibus address
126
bc.up
Behaviour as backup controller
0
0
No backup functionality
1
With backup functionality