3.4 Error list / Maintenance manager

With one or several errors, the extended

operating level always starts with the error list.

Signalling an actual entry in the error list (alarm,

error) is done by the Err LED in the display. To

reach the error list press Ù twice.

Error list:

Operation

8840 profiler

13

Error list / Maintenance manager

RUN

°C

°F

Err LED status Signification

Proceed as follows

blinks(status 2) Alarm due to existing

error

Determine the error type in the error list After error

correction the unit changes to status 1

lit(status 1)

Error removed, alarm

not acknowledged

Acknowledge the alarm in the error list pressing key

È

or

Ì

The alarm entry was deleted (status 0).

off(status 0)

No error, all alarm

entries deleted

-Not visible except when acknowledging

Name

Description

Reason

Possible remedial action

E.1

Internal error,

cannot be removed

- E.g. defective EEPROM - Contact West service

- Return unit to our factory

E.2

Internal error, can be

reset

- e.g. EMC trouble

- Keep measurement and power

supply cables in separate runs

- Ensure that interference

suppression of contactors is

provided

E.3

Configuration error,

can be reset

- wrong configuration

- missing configuration

- Check interaction of configuration

/ parameters

E.4

Hardware error

- Codenumber and

hardware are not

identical

- Contact West service

- Elektronic-/Optioncard must be

exchanged

FbF.1

Sensor break INP1 - Sensor defective

- Faulty cabling

- Replace INP1 sensor

- Check INP1 connection

Sht.1

Short circuit INP1 - Sensor defective

- Faulty cabling

- Replace INP1 sensor

- Check INP1 connection

POL.1

INP1polarity error - Faulty cabling

- Reverse INP1 polarity

FbF.2

Sensor break INP2 - Sensor defective

- Faulty cabling

- Replace INP2 sensor

- Check INP2 connection

Sht.2

Short circuit INP2 - Sensor defective

- Faulty cabling

- Replace sensor INP2

- Check INP2 connection

POL.2

INP2 polarity

- Faulty cabling

- Reverse INP2 polarity

FbF.3

Sensor break INP3 - Sensor defective

- Faulty cabling

- Replace INP3 sensor

- Check INP3 connection

Sht.3

Short circuit INP3 - Sensor defective

- Faulty cabling

- Replace sensor INP3

- Check INP3 connection

POL.3

INP3 polarity

- Faulty cabling

-

- Reverse INP3 polarity