2 parameters 66, Prog, 2 parameters – West Control Solutions N8840 User Manual
Page 66
7.2 Parameters
Programmer level
Parameters
66
8840 profiler
ProG
Name
Value Range Description
Default
b.Lo
0...9999
Bandwidth lower limit
Off
b.Hi
0...9999
Bandwidth upper limit
Off
d.00
Resetvalue of control track 1 ... 4
0
0
track 1= 0; track 2= 0; track 3= 0; track 4= 0
1
track 1= 1; track 2= 0; track 3= 0; track 4= 0
2
track 1= 0; track 2= 1; track 3= 0; track 4= 0
3
track 1= 1; track 2=1; track 3= 0; track 4=0
4
track 1= 0; track 2= 0; track 3= 1; track 4= 0
5
track 1= 1; track 2= 0; track 3= 1; track 4= 0
6
track 1= 0; track 2= 1; track 3= 1; track 4= 0
7
track 1= 1; track 2= 1; track 3= 1; track 4= 0
8
track 1= 0; track 2= 0; track 3= 0; track 4= 1
9
track 1= 1; track 2= 0; track 3= 0; track 4=1
10
track 1= 0; track 2= 1; track 3= 0; track 4= 1
11
track 1= 1; track 2= 1; track 3= 0; track 4= 1
12
track 1= 0; track 2= 0; track 3= 1; track 4= 1
13
track 1= 1; track 2= 0; track 3= 1; track 4= 1
14
track 1= 0; track 2= 1; track 3= 1; track 4= 1
15
track 1= 1; track 2= 1; track 3= 1; track 4= 1
tYPE
segment type 1
0
0
time
1
gradient
2
hold
3
step
4
time and wait
5
gradient and wait
6
hold and wait
7
step and wait
8
end segment
SP
-1999...9999
segment end set-point 1
Pt
0...9999
segment time/-gradient 1
d.Out
control track 1...4 - 1 (see parameter d.00)
tYPE
segment type 2
(see segment type 1)
0
SP
-1999...9999
segment end set-point 2
Pt
0...9999
segment time/-gradient 2
d.Out
control track 1...4 - 2 (see parameter d.00)
tYPE
segment type3
(see segment type 1)
0
SP
-1999...9999
segment end set-point3
Pt
0...9999
segment time/-gradient 3
d.Out
control track 1...4 - 3 (see parameter d.00)
tYPE
segment type 4
(see segment type 1)
0
SP
-1999...9999
segment end set-point 4
Pt
0...9999
segment time/-gradient 4
d.Out
control track 1...4 - 4 (see parameter d.00)