Configuration 40, Out.4, Out.5 – West Control Solutions N8840 User Manual
Page 40: Out.6, Logi

Configuration level
Configuration parameters
40
8840 profiler
Name
Value range Description
Default
CAll
Operator call
0
0
not active
1
active
Out.0
-1999...9999
Scaling of the analog output for 0% (0/4mA or 0/2V, only
visible when O.TYP=1..5)
0
Out.1
-1999...9999
Scaling of the analog output for 100% (20mA or 10V, only
visible when O.TYP=1..5)
100
O.Src
Signal source of the analog output OUT3 (only visible when
O.TYP=1..5)
1
0
not used
1
controller output y1 (continuous)
2
controller output y2 (continuous)
3
process value
4
effective set-point Weff
5
control deviation xw (process value - set-point)
6
measured value position feedback Yp
7
measured value INP1
8
measured value INP2
9
measured value INP3
fOut
Forcing OUT3 (only visible with 8800/8840 Configurator!)
0
0
No forcing
1
Forcing via serial interface
Out.4
Configuration parameters Out.4 as Out.3
Out.5
Configuration parameters Out.2 as Out.1 except for: Default Y.1 = 0 Y.2 = 0
Out.6
Configuration parameters Out.2 as Out.1 except for: Default Y.1 = 0 Y.2 = 0
g
Method of operation and usage of output Out.1 to Out.6:
Is more than one signal chosen active as source, those signals are OR-linked.
LOGI
Name
Value range Description
Default
L_r
Local / Remote switching (Remote: adjusting of all values
by front keys is blocked)
0
0
no function (switch-over via interface is possible)
1
always active
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è - key switches