beautypg.com

Technical data 80, Technical data – West Control Solutions N8840 User Manual

Page 80

background image

CONTROL INPUTS DI2, DI3 (OPTION)

The digital input di2 located on the A-card and

di2 located on the option card are or-linked.

Configurable as switch or push-button!

Optocoupler input for active triggering.

Nominal voltage

24 V DC external

Current sink (IEC 1131 type 1)

Logic “0”

-3...5 V

Logic “1”

15...30 V

Current requirement

approx.. 5 mA

TRANSMITTER SUPPLY U

T

(OPTION)

Power:

22 mA / ≥ 18 V

If the universal output OUT3 or OUT4 is used

there may be no external galvanic connection

between measuring and output circuits!

GALVANIC ISOLATION

Safety isolation

Function isolation

OUTPUTS

RELAY OUTPUTS OUT1...OUT4

Contact type:

potential-free changeover

contact

Max.contact rating:

500 VA, 250 V, 2A at 48...62

Hz,

resistive load

Min. contact rating:

5V, 10 mA AC/DC

Operating life (electr.): 600.000 duty cycles with

max. contact rating

Note:
If the relays operate external contactors, these

must be fitted with RC snubber circuits to

manufacturer specifications to prevent

excessive switch-off voltage peaks.

OUT3, 4 AS UNIVERSAL OUTPUT

Galvanically isolated from the inputs.

Freely scalable resolution:

11 bits

Current output

0/4...20 mA configurable.

Signal range:

0...approx.22mA

Max. load:

≤ 500 Ω

Load effect:

no effect

Resolution:

≤ 22 µA (0,1%)

Accuracy

≤ 40 µA (0,2%)

Voltage output

0/2...10V configurable

Signal range:

0...11 V

Min. load:

≥ 2 kΩ

Load effect:

no effect

Resolution:

≤ 11 mV (0,1%)

Accuracy

≤ 20 mV (0,2%)

OUT3, 4 used as transmitter supply

Output power:

22 mA / ≥ 13 V

OUT3, 4 used as logic output

Load ≤ 500 Ω

0/≤ 20 mA

Load > 500 Ω

0/> 13 V

OUTPUTS OUT5/6 (OPTION)

Galvanically isolated opto-coupler outputs.

Grounded load: common positive voltage.

Output rating: 18...32 VDC; ≤ 70 mA

Internal voltage drop: ≤ 1 V with I

max

Protective circuit: built-in against short circuit,

overload, reversed polarity (free-wheel diode

for relay loads).

Technical data

80

8840 profiler

Process value input INP1

Mains supply

Supplementary input INP2
Optional input INP3
Digital input di1, di2

Relay OUT1

RS422/485 interface

Relay OUT2

Digital inputs di2, 3 option

Relay OUT3

Universal output OUT3

Relay OUT4

Universal output OUT4
Transmitter supply U

T

OUT5, OUT6