Configuration 33, Inp.2, Inp.3 – West Control Solutions N8840 User Manual
Page 33
Configuration level
8840 profiler
33
Configuration parameters
InP.2
Name
Value range Description
Default
I.Fnc
Function selection of INP2
1
0
no function (subsequent input data are skipped)
1
heating current input
2
External set-point SP.E (switch-over -> LOGI/ SP.E)
3
Position feedback Yp
4
Second process value x2 (ratio, min, max, mean)
5
External positioning value Y.E
(switch-over r LOGI / Y.E)
6
no controller input (e.g. transmitter input instead)
7
Process value x1
S.tYP
Sensor type selection
30
30
0...20mA / 4...20mA 1
31
0...50mA AC 1
50
Potentiometer ( 0...160 Ohm) 1
51
Potentiometer ( 0...450 Ohm) 1
52
Potentiometer ( 0...1600 Ohm) 1
53
Potentiometer ( 0...4500 Ohm) 1
Corr
Measured value correction / scaling
0
0
Without scaling
1
Offset correction (at CAL level)
2
2-point correction (at CALlevel)
3
Scaling (at PArA level)
In.F
-1999...9999
Alternative value for error at INP2
OFF
fAI2
Forcing INP2 (only visible with 8800/8840 Configurator!)
0
0
No forcing
1
Forcing via serial interface
InP.3
Name
Value range Description
Default
I.Fnc
Function selection of INP3
1
0
no function (subsequent input data are skipped)
1
heating current input
2
External set-point SP.E (switch-over -> LOGI/ SP.E)
3
Yp input
4
Second process value X2
5
External positioning value Y.E
(switch-over r LOGI / Y.E)
6
no controller input (e.g. transmitter input instead)
7
Process value x1