7.3 Programmer description

7.3.1 General

A survey of the most important features:

w Programs:

8 or 16 (dependent of order)

w Control outputs:

4

w Segments:

16 per program

w Segment types:

ramp (set-point and time)

ramp (set-point and gradient)

hold segment (holding time)

step segment (with alarm suppression)

end segment

All segment types can be combined with ”Wait at the end and call operator”

w Time unit:

configurable in hours:minutes or

minutes:seconds

w Maximum

segment duration: 9999 hours = 1 year 51 days

w Maximum

program duration: 16 x 9999 hours = > 18 years

w Gradient:

0,01°C/h ( /min) to 9999°C/h ( /min)

w Program name:

8 characters, adjustable via

8800/8840 Configurator software

w Bandwidth control: bandwidth high and low (b.Lo,b.Hi)

limits defininable for each program

Programmer level

Programmer description

68

8840 profiler

b.Hi

b.Lo

hold segment

step segment

analog track

control track 1

control track 2

control track 3

control track 4

1

2

4

5

12

13

14

15

16 (8)

16

PRESET END

PRESET

RESET

START

END

program time run off

3

program end