3 programmer description 68, 1 general 68, 3 programmer description – West Control Solutions N8840 User Manual
Page 68
7.3 Programmer description
7.3.1 General
A survey of the most important features:
w Programs:
8 or 16 (dependent of order)
w Control outputs:
4
w Segments:
16 per program
w Segment types:
ramp (set-point and time)
ramp (set-point and gradient)
hold segment (holding time)
step segment (with alarm suppression)
end segment
All segment types can be combined with ”Wait at the end and call operator”
w Time unit:
configurable in hours:minutes or
minutes:seconds
w Maximum
segment duration: 9999 hours = 1 year 51 days
w Maximum
program duration: 16 x 9999 hours = > 18 years
w Gradient:
0,01°C/h ( /min) to 9999°C/h ( /min)
w Program name:
8 characters, adjustable via
8800/8840 Configurator software
w Bandwidth control: bandwidth high and low (b.Lo,b.Hi)
limits defininable for each program
Programmer level
Programmer description
68
8840 profiler
b.Hi
b.Lo
hold segment
step segment
analog track
control track 1
control track 2
control track 3
control track 4
1
2
4
5
12
13
14
15
16 (8)
16
PRESET END
PRESET
RESET
START
END
program time run off
3
program end