2 parameters 58, Parameters 58 - 60, Cntr – West Control Solutions N8840 User Manual
Page 58: Par.2, 2 parameters
5.2 Parameters
1 Valid for ConF/ othr/ dP = 0. With dP = 1 / 2 / 3 also 0,1 / 0,01 /
0,001 is possible.
Parameter setting level
Parameters
58
8840 profiler
Cntr
Name
Value range Description
Default
Pb1
1...9999 1
Proportional band 1 (heating) in phys. dimensions (e.g. °C)
100
Pb2
1...9999 1
Proportional band 2 (cooling) in phys. dimensions (e.g. °C)
100
ti1
0,1...9999
Integral action time 1 (heating) [s]
180
ti2
0,1...9999
Integral action time 2 (cooling) [s]
180
td1
0,1...9999
Derivative action time 1 (heating) [s]
180
td2
0,1...9999
Derivative action time 2 (cooling) [s]
180
t1
0,4...9999
Minimal cycle time 1 (heating) [s]. The minimum impulse is
1/4 x t1
10
t2
0,4...9999
Minimal cycle time 2 (heating) [s]. The minimum impulse is
1/4 x t2
10
SH
0...9999
Neutral zone or switching differential for on-off control
[phys. dimensions)
2
Hys.l
0...9999
Switching difference Low signaller [engineering unit]
1
Hys.H
0...9999
Switching difference High signaller [engineering unit]
1
d.SP
-1999...9999
Trigger point seperation for additional contact ∆ / Y / Off
[phys. dimensions]
100
tP
0,1...9999
Minimum impulse [s]
OFF
tt
3...9999
Motor travel time [s]
60
Y2
-100...100
2. correcting variable
0
Y.Lo
-120...120
Lower output limit [%]
0
Y.Hi
-120...120
Upper output limit [%]
100
Y.0
-100...100
Working point for the correcting variable [%]
0
Ym.H
-100...100
Limitation of the mean value Ym [%]
5
L.Ym
0...9999
Max. deviation xw at the start of mean value calculation
[phys. dimensions]
8
oFFS
-120...120
Zero offset
0
PAr.2
(second parameterset
r
5.4)
Name
Value range Description
Default
Pb12
1...9999 1
Proportional band 1 (heating) in phys. dimensions (e.g. °C),
2. parameter set
100
Pb22
1...9999 1
Proportional band 2 (cooling) in phys. dimensions (e.g. °C),
2. parameter set
100
Ti22
0,1...9999
Integral action time 2 (cooling) [s], 2. parameter set
180