Configuration 37, Out.1 – West Control Solutions N8840 User Manual
Page 37

Configuration level
8840 profiler
37
Configuration parameters
Name
Value range Description
Default
HC.AL
Alarm heat current function (INP2)
0
0
switched off
1
Overload short circuit monitoring
2
Break and short circuit monitoring
LP.AL
Monitoring of control loop interruption for heating
0
0
switched off / inactive
1
active.
If ti1=0 LOOP alarm is inactive!
Hour
OFF...999999
Operating hours (only visible with 8800/8840 Configurator!)
OFF
Swit
OFF...999999
Output switching cycles (only visible with 8800/8840
Configurator!)
OFF
Out.1
Name
Value range Description
Default
O.Act
Method of operation of output OUT1
0
0
direct / normally open
1
inverse / normally closed
Y.1
Controller output Y1
1
0
not active
1
active
Y.2
Controller output Y2
0
0
not active
1
active
Lim.1
Limit 1 signal
0
0
not active
1
active
Lim.2
Limit 2 signal
0
0
not active
1
active
Lim.3
Limit 3 signal
0
0
not active
1
active
LP.AL
Interruption alarm signal (LOOP)
0
0
not active
1
active
HC.AL
Heat current alarm signal
0
0
not active
1
active
HC.SC
Solid state relay (SSR) short circuit signal
0
0
not active
1
active
P.EnD
Message "Programm end"
0
0
not active
1
active
FAi.1
INP1 error signal
0
0
not active
1
active