3 selecting the method ( conf / cntr / tune ) 17 – West Control Solutions N8840 User Manual
Page 17
Optimization at the set-point: (see page 18)
For optimizing at the set-point, the controller outputs a disturbance variable to the
process. This is done by changing the output variable shortly. The process value
changed by this pulse is evaluated. The detected process parameters are
converted into control parameters and saved in the controller.
This procedure optimizes the control loop directly at the set-point. The advantage
is in the small control deviation during optimization.
3.5.3 Selecting the method ( ConF/ Cntr/ tunE)
Selection criteria for the optimization method:
Step attempt after start-up
Pulse attempt after start-up Optimization at the set-point
tunE = 0
sufficient set-point reserve is
provided
sufficient set-point reserve is not
provided
tunE = 1
sufficient set-point reserve is
provided
sufficient set-point reserve is not
provided
tunE = 2
always step attempt after
start-up
Sufficient set-point reserve:
inverse controller: (with process value < set-point- (10% of rnGH - rnGL)
direct controller:
(with process value > set-point + (10% of rnGH - rnGL)
Step attempt after start-up
Condition:
- tunE = 0 and sufficient set-point reserve provided or
- tunE = 2
The controller outputs 0% correcting variable or Y.Lo and waits, until the process
is at rest (see start-conditions on page 15).
Subsequently, a correcting variable step change to 100% is output.
The controller attempts to calculate the optimum control parameters from the
process response. If this is done successfully, the optimized parameters are taken
over and used for line-out to the set-point.
With a 3-point controller, this is followed by “cooling”.
After completing the 1st step as described, a correcting variable of -100% (100%
cooling energy) is output from the set-point. After successfull determination of
the “cooling parameters”, line-out to the set-point is using the optimized
parameters.
Operation
8840 profiler
17
Self-tuning