Parameters 59, Setp, Inp.1 – West Control Solutions N8840 User Manual
Page 59: Inp.2, Inp.3
1 Valid for ConF/ othr/ dP = 0. With dP = 1 / 2 / 3 also 0,1 / 0,01 /
0,001 is possible.
Parameter setting level
8840 profiler
59
Parameters
Name
Value range Description
Default
Ti12
0,1...9999
Integral action time 1 (heating) [s], 2. parameter set
180
Td12
0,1...9999
Derivative action time 1 (heating) [s], 2. parameter set
180
Td22
0,1...9999
Derivative action time 2 (cooling) [s], 2. parameter set
180
SEtP
Name
Value range Description
Default
SP.LO
-1999...9999
Set-point limit low for Weff
-100
SP.Hi
-1999...9999
Set-point limit high for Weff
1200
SP.2
-1999...9999
Set-point 2.
0
r.SP
0...9999
Set-point gradient [/min]
OFF
SP
-1999...9999
Set-point (only visible with 8800/8840 Configurator!)
0
SP.LO and SP.Hi should be within the limits of rnGH and rnGL see
configuration r Controller page 18
InP.1
Name
Value range Description
Default
InL.1
-1999...9999
Input value for the lower scaling point
0
OuL.1
-1999...9999
Displayed value for the lower scaling point
0
InH.1
-1999...9999
Input value for the upper scaling point
20
OuH.1
-1999...9999
Displayed value for the lower scaling point
20
t.F1
0,0...9999
Filter time constant [s]
0,5
Etc.1
0...100 (°C)
32...212 (°F)
External cold-junction reference temperature (external TC)
OFF
InP.2
Name
Value range Description
Default
InL.2
-1999...9999
Input value for the lower scaling point
0
OuL.2
-1999...9999
Displayed value for the lower scaling point
0
InH.2
-1999...9999
Input value for the upper scaling point
50
OuH.2
-1999...9999
Displayed value for the upper scaling point
50
t.F2
0,0...999,9
Filter time constant [s]
0,5
InP.3
Name
Value range Description
Default
InL.3
-1999...9999
Input value for the lower scaling point
0
OuL.3
-1999...9999
Displayed value for the lower scaling point
0
InH.3
-1999...9999
Input value for the upper scaling point
20