TM 40/40R, Rev (4) November 2010

40/40R Optical Flame Detector

63

E.1.2.4 Other

1

The complete function of the flame detector (flame detection, function of

the 0-20mA interface, the relays) must be examined at least every six or

twelve months (see The SharpEye 40/40RSafety Relevant Parameters on

page 61, when the flame detector must be switched OFF and ON.

2

The window of the sensor must be examined at appropriate time

intervals for partial contamination.

3

The HART and the RS 485/IrDA interfaces must not be used for the

transmission of the safety-related data.