beautypg.com

2 troubleshooting – Spectrex 40/40R - Single IR Flame Detector User Manual

Page 49

background image

TM 40/40R, Rev (4) November 2010

Troubleshooting

37

4.2 Troubleshooting

This section is intended to be a guide to correct problems which may happen

during normal operation.
Table 19: Troubleshooting Table

Problem

Cause

Corrective Action

LEDs Off
Fault Relay at N.O

0-20mA at 0mA

No power at the
unit

Check that the correct power
is sent to the detector.

Check power polarity.

Check wiring in the detector.

Send the detector back for
repairs.

Yellow LED flashes
at 4 Hz

Fault Relay at N.O

0-20mA at 0mA

Fault Detector

Low Voltage

Faulty Detector

Check the voltage at the
detector; verify at least 24V

at the detector terminal.

Send the detector back for

repairs.

Yellow LED flashes
at 4 Hz

Fault Relay at N.O
0-20mA at 2mA

BIT Fault

Faulty Detector

Clean detector window.

Re-power the detector.

Replace the detector.

Red LED

constantly on

If no fire exists,

then, detector
alarm latched

Perform Reset to the detector.

Alarm Relay at On
0-20mA at 20mA

Alarm condition

Check cause for alarm.

If no alarm, re-power the

detector.

Send the detector back for

repairs.