SharpEye

TM

Single IR Flame Detector User Guide

12 Performance

Considerations

1.5.6 Detector

Status

The possible detector function statuses are listed in Table 6. A more detailed
fault analysis can be seen via HART or RS485.
Table 6: Detector Status

Status

Description

Normal Normal

operation.

BIT Built-In-Test

being

performed.

Warning

Fire detected - changed to Warning (pre-alarm state).

Alarm

Fire detected - changed to Fire Alarm state.

Latched Alarm

(Optional)

The alarm outputs remain latched on following detection

of a fire that has already been extinguished.

BIT Fault

A fault is detected during BIT sequence or other electric
failure. The detector will continue to detect for fire.

Fault

A fault is detected when the power supply is too low or
due to a software fault or electrical failure. The detector

will NOT detect fire in this condition.

In each state, the detector activates different outputs, as specified in

Table 7.
Table 7: Output Signals versus Detector State

Detector

State

LED

Indicator

LED

Mode

Alarm

Relay

Auxiliary

Relay

Fault

Relay

mA

output

Normal Green

1Hz

Off Off On

4

mA

Warning Red 2Hz Off On

(4)

On

16

mA

Alarm

(1)

Red

Constant

On On On

20

mA

Off On

20

mA

Latch

(2)

Red

Constant

On

On

(4)

On

20

mA

BIT Fault

(3)

Yellow

4Hz

Off

Off

Off 2

mA

Warning at

BIT Fault

Red 2Hz Off On

(4)

Off

16

mA

Alarm at

BIT Fault

Red Constant

On On Off

20

mA

Fault Yellow

4Hz

Off

Off

Off

0

mA

Notes:

1

The alarm outputs are activated while alarm conditions exist and will

stop approximately 5 seconds after the fire is no longer detected.

2

The Alarm state can be optionally latched via programmed function.

(Default is non-latching).

3

The detector will remain in BIT Fault state until it has passed a
successful BIT.