6 detector status – Spectrex 40/40R - Single IR Flame Detector User Manual
Page 24
SharpEye
TM
Single IR Flame Detector User Guide
12 Performance
Considerations
1.5.6 Detector
Status
The possible detector function statuses are listed in Table 6. A more detailed
fault analysis can be seen via HART or RS485.
Table 6: Detector Status
Status
Description
Normal Normal
operation.
BIT Built-In-Test
being
performed.
Warning
Fire detected - changed to Warning (pre-alarm state).
Alarm
Fire detected - changed to Fire Alarm state.
Latched Alarm
(Optional)
The alarm outputs remain latched on following detection
of a fire that has already been extinguished.
BIT Fault
A fault is detected during BIT sequence or other electric
failure. The detector will continue to detect for fire.
Fault
A fault is detected when the power supply is too low or
due to a software fault or electrical failure. The detector
will NOT detect fire in this condition.
In each state, the detector activates different outputs, as specified in
Table 7.
Table 7: Output Signals versus Detector State
Detector
State
LED
Indicator
LED
Mode
Alarm
Relay
Auxiliary
Relay
Fault
Relay
mA
output
Normal Green
1Hz
Off Off On
4
mA
Warning Red 2Hz Off On
(4)
On
16
mA
Alarm
(1)
Red
Constant
On On On
20
mA
Off On
20
mA
Latch
(2)
Red
Constant
On
On
(4)
On
20
mA
BIT Fault
(3)
Yellow
4Hz
Off
Off
Off 2
mA
Warning at
BIT Fault
Red 2Hz Off On
(4)
Off
16
mA
Alarm at
BIT Fault
Red Constant
On On Off
20
mA
Fault Yellow
4Hz
Off
Off
Off
0
mA
Notes:
1
The alarm outputs are activated while alarm conditions exist and will
stop approximately 5 seconds after the fire is no longer detected.
2
The Alarm state can be optionally latched via programmed function.
(Default is non-latching).
3
The detector will remain in BIT Fault state until it has passed a
successful BIT.