40/40R Optical Flame Detector

61

E SIL-2

Features

In this appendix…

40/40R Optical Flame Detector

page 61

E.1

40/40R Optical Flame Detector

This appendix details the special conditions to comply with the requirements
of EN 61508 for SIL-2.
The SharpEye 40/40R shall only be used in low demand mode application,
see IEC 61508.4, Chapter 3.5.12.

E.1.1

Safety Relevant Parameters

Perform the following functional checks of the detector:
Alternative 1: Functional check of the detector every 180 days:

HFT: 0
PFD: 2.4 x 10

-4

(≈ 2.4% of SIL-2) if only Alarm Relay is used for

alerting.

PFD: 2.6 x 10

-4

(≈ 2.6% of SIL-2) if 0-20mA interface is used.

SFF: 95% fulfills the conditions of EN 61508 for SIL2

Alternative 2: Functional check of the detector every 365 days:

HFT: 0
PFD: 3.2 x 10

-4

(≈ 3.2% of SIL-2) if only Alarm Relay is used for

alerting.

PFD: 3.6 x 10

-4

(≈ 3.6% of SIL-2) if 0-20mA interface is used to

signal current as alarm.

SFF: 95% fulfills the conditions of EN 61508 for SIL2

E.1.2

Guidelines for Configuring, Installing, Operating and
Service

The alert conditions according to SIL 2 can be implemented by an:
• Alert signal via 20mA current loop

or

• Alert signal via alarm relay and the fault relay