3 false alarms prevention – Spectrex 40/40R - Single IR Flame Detector User Manual

Page 21

background image

TM 40/40R, Rev (4) November 2010

Performance Considerations

9

1.5.3 False

Alarms

Prevention

To prevent false alarms, the detector will not alarm or react to the radiation

sources specified in Table 3.
Table 3: Immunity to False Alarm Sources

Radiation Source

Immunity
Distance ft. (m)

Vehicle headlights (low beam) conforming to
MS53023-1

1.7 (0.5)

Incandescent frosted glass light100 W

1.7 (0.5)

Fluorescent light with white enamel reflector, standard
office or shop, 70 W (or two 35 W)

IAD

Arc welding [6 mm (

5

/

16

") rod; 210 A]

11.5 (3.5)

Grinding metal

1.7 (0.5)

Lit cigar

3.3 (1)

Lit cigarette

1.7 (0.5)

Match, wood, stick including flare up

3.3 (1)

Notes:
• IAD = Immune at Any Distance.
• All sources are chopped from 0 to 20 Hz.