3 false alarms prevention – Spectrex 40/40R - Single IR Flame Detector User Manual
Page 21
TM 40/40R, Rev (4) November 2010
Performance Considerations
9
1.5.3 False
Alarms
Prevention
To prevent false alarms, the detector will not alarm or react to the radiation
sources specified in Table 3.
Table 3: Immunity to False Alarm Sources
Radiation Source
Immunity
Distance ft. (m)
Vehicle headlights (low beam) conforming to
MS53023-1
1.7 (0.5)
Incandescent frosted glass light100 W
1.7 (0.5)
Fluorescent light with white enamel reflector, standard
office or shop, 70 W (or two 35 W)
IAD
Arc welding [6 mm (
5
/
16
") rod; 210 A]
11.5 (3.5)
Grinding metal
1.7 (0.5)
Lit cigar
3.3 (1)
Lit cigarette
1.7 (0.5)
Match, wood, stick including flare up
3.3 (1)
Notes:
• IAD = Immune at Any Distance.
• All sources are chopped from 0 to 20 Hz.