TM 40/40R, Rev (4) November 2010

Troubleshooting

43

Option 3: Power, RS-485, 0-20mA (Source) and

HART protocol, Fault Relay (N.O), Alarm Relay (N.O,

N.C).

Option 4: Power, RS-485, Fault Relay (N.C), Auxiliary
Relay (N.O), Alarm Relay, (N.O).

Option 5: Power, RS-485, Fault Relay (N.O),

Auxiliary Relay (N.O), Alarm Relay, (N.O).

Electrical
Outputs

Dry Contact Relays

Table 21: Contact Ratings

Relay

Name

Type

Normal

Position

Maximum

Ratings

Alarm DPST

N.O.,

N.C.

2A at 30

VDC or

0.5A at

250 VAC

Auxiliary SPST

N.O.

5A at 30

VDC or

250 VAC

Fault *

SPST

N.C. or

N.O

5A at 30

VDC or
250 VAC

Notes:
• The Fault relay (in wiring options 1, 2, 4) is

normally energized closed during normal operation
of the detector. The relay is de-energized open if a

fault condition or low voltage situation occurs.

• * In wiring options 3, 5 the relay is normally

energized open during normal operation of the

detector. The relay is de-energized close contact if
a fault condition or low voltage situation occurs.

0-20mA Current Output: The 0-20mA can be Sink

or Source according to the wiring option source (see

General Instructions for Electrical Wiring on page 47).

The maximum permitted load resistance is 600Ω.

Table 22: 20 mA Current Output

State

Output

Fault

0 +1 mA

BIT Fault

2 mA±10%

Normal 4

mA±10%

Warning 16

mA

5%

Alarm 20

mA±5%