Connecting the Detector

25

2.7

Connecting the Detector

This section describes how to connect the electric cabling to the detector

(Figure 6).

To connect the detector to the electrical cables

1

Disconnect the power.

2

Remove the back cover of the detector by removing four (4) socket

head-screws in the cover bolts. The terminal chamber is now revealed.

3

Remove the protective plug mounted on the Detector Conduit/Cable

entry; pull the wires through the Detector Inlet.

4

Use a ¾" – 14 NPT explosion-proof conduit connection or M25x1.5

flameproof gland to assemble the cable / conduit to the detector.

Figure 6: Detector with Cover Removed

5

Connect the wires to the required terminals on the Terminal Board
according to the wiring diagram (Figure 6) and Table 15.

6

Connect the grounding (earth) wire to the ground (earth) screw outside
the detector (Earth Terminal). The detector must be well grounded to

earth ground.

7

Verify the wiring. Improper wiring may damage the detector.

Earth
Terminal

Terminal

Chamber

Terminals

Internal Earth
Terminal

Detector Holding

Screw
Conduit / Cable

Inlet