This chapter describes how to power up and test the detector. It also
includes some very important safety checks that you should make before

operating the detector.

3.1 Powering

Up

This section describes how to power up the detector. Follow these

instructions carefully to obtain optimal performance from the detector over

its life cycle:

To power up the detector:

1

Turn on the power.

2

Wait approximately 60 seconds for the detector to finish the start-up

procedure.
Applying power initiates the following sequence of events:
• The yellow LED flashes at 4 Hz.
• BIT is executed.
If successful, the green LED flashes at 1 Hz and the FAULT relay contacts

close, mA output is 4 mA.

3

Enter to Normal mode.

Note: The majority of detectors are used in the default non-latching alarm

mode. Only perform a Reset when the Latching alarm option has been

programmed.

To reset a detector when in it is in a LATCHED ALARM state:
• Do one of the following:

• Disconnect power (Terminal Number 1 or Terminal Number 2).

or

• Initiate a Manual BIT.