TM 40/40R, Rev (4) November 2010

Performance Considerations

11

1.5.5 Output

Signals

Outputs are available according to the default configuration or the wiring

options selected for the 40/40R detector. Determine the outputs for your

model according to Table 5.
The detector incorporates several types of output suitable to different

control systems:
• 0-20mA (stepped) with HART
• Relays (Alarm, Fault, Auxiliary)
• RS-485 Modbus
Table 5: Available Output Types

Output Type

Version

Detector Status

40/40R – Options 1XXXX,
4XXXX, 5XXXX

The relay is N.O.

Alarm relay

40/40R – Options 2XXXX,
3XXXX

The relay is N.O. and N.C.

Auxiliary relay

40/40R – Options 4XXXX

and 5XXXX

The relay is N.O.

40/40R – Options 1XXXX,

2XXXX, 4XXXX

The relay is N.C. energized

Fault relay

40/40R – Options 3XXXX,

5XXXX

The relay is N.O. energized

40/40R – Option 1XXXX

SINK Option, (can be
changed to Source – see

Figure 9, Figure 10 and
Figure 11)

0-20mA
current output

40/40R – Options 2XXXX

and 3XXXX

SOURCE Option with the

HART protocol

RS-485

All versions

Modbus protocol