beautypg.com

4 certification instructions – Spectrex 40/40R - Single IR Flame Detector User Manual

Page 32

background image

SharpEye

TM

Single IR Flame Detector User Guide

20 Certification

Instructions

2.4 Certification

Instructions

Warning: Do not open the detector, even when isolated, when

flammable atmosphere present.

Use the following certification instructions:
• The cable entry point may exceed 167°F (75°C). Suitable precautions

should be taken when selecting the cable.

• The equipment may be used with flammable gases and vapors with

apparatus groups IIA and IIB + H2:

• T5 in the ambient temperature range: –67°F (–55°C) to +167°F

(+75°C).

• T4 in the ambient temperature range: –67°F (–55°C) to +185°F

(+85°C).

• Installation shall be carried out by suitably trained personnel in

accordance with the applicable code of practice such as. EN 60079-

14:1997.

• Inspection and maintenance of this equipment shall be carried out by

suitably trained personnel in accordance with the applicable code of

practice such as EN 60079-17.

• Repair of this equipment shall be carried out by suitably trained

personnel in accordance with the applicable code of practice such as EN

60079-19.

• The certification of this equipment relies upon the following materials

used in its construction:

Enclosure: 316L Stainless Steel or Aluminum
Window: Sapphire Glass

• If the equipment is likely to come into contact with aggressive

substances, then it is the responsibility of the user to take suitable

precautions that prevent it from being adversely affected, thus ensuring

that the type of protection provided by the equipment is not

compromised:

• Aggressive substances: acidic liquids or gases that may attack

metals, or solvents that may affect polymeric materials.

• Suitable precautions: regular checks as part of routine inspections or

establishing from the material’s data sheets that it is resistant to

specific chemicals.