A.2 electrical specifications, A.3 outputs – Spectrex 40/40R - Single IR Flame Detector User Manual
Page 54
SharpEye
TM
Single IR Flame Detector User Guide
42
Outputs
A.2 Electrical
Specifications
Table 20: Electrical Specifications
Operating
Voltage
Status
All
Outputs
Without
0-20mA
Normal 1.61W
1.56W
Normal when Heater On
2.28W
2.16W
Alarm
2.64W
2.28W
Power
Consumption
(Max. 24VDC)
Alarm when Heater On
3.24W
2.88W
Normal 70mA
65mA
Normal when Heater On
95mA
90mA
Alarm 110mA
95mA
Maximum Current
(Max. 24VDC)
Alarm when Heater On
135mA
120mA
Normal 1.95W
1.85W
Normal when Heater On
2.56W
2.45W
Alarm 3.04W
2.56W
Power
Consumption
(Max. 18-32VDC)
Alarm when Heater On
3.68W
3.2W
Normal 90mA
85mA
Normal when Heater On
105mA
100mA
Alarm 130mA
115mA
Maximum Current
(18-32VDC)
Alarm when Heater On
160mA
145mA
Electrical Input Protection The input circuit is protected against
voltage-reversed polarity, voltage transients,
surges and spikes according to MIL-STD-
1275B
A.3 Outputs
Electrical
Interface
There are five output-wiring options. These options must
be defined at the factory per the customer order and
cannot be changed at the customer facility.
See General Instructions for Electrical Wiring on page 47
for the wiring/terminal diagram for each option.
Unless otherwise specified, the default is Option 1. The
wiring arrangement is identified on the detector by the
part number (see Model and Types on page 2).
•
Option 1: Power, RS-485, 0-20mA (Sink), Fault I
Relay (N.C), Alarm Relay, (N.O) (see Figure 6).
•
Option 2: Power, RS-485, 0-20mA (Source) and
HART protocol, Fault Relay (N.O), Alarm Relay, (N.O),
(N.C).