Outputs

A.2 Electrical

Specifications

Table 20: Electrical Specifications

Operating

Voltage

Status

All

Outputs

Without

0-20mA

Normal 1.61W

1.56W

Normal when Heater On

2.28W

2.16W

Alarm

2.64W

2.28W

Power

Consumption

(Max. 24VDC)

Alarm when Heater On

3.24W

2.88W

Normal 70mA

65mA

Normal when Heater On

95mA

90mA

Alarm 110mA

95mA

Maximum Current
(Max. 24VDC)

Alarm when Heater On

135mA

120mA

Normal 1.95W

1.85W

Normal when Heater On

2.56W

2.45W

Alarm 3.04W

2.56W

Power

Consumption
(Max. 18-32VDC)

Alarm when Heater On

3.68W

3.2W

Normal 90mA

85mA

Normal when Heater On

105mA

100mA

Alarm 130mA

115mA

Maximum Current
(18-32VDC)

Alarm when Heater On

160mA

145mA


Electrical Input Protection
The input circuit is protected against

voltage-reversed polarity, voltage transients,

surges and spikes according to MIL-STD-

1275B

A.3 Outputs

Electrical
Interface

There are five output-wiring options. These options must
be defined at the factory per the customer order and

cannot be changed at the customer facility.
See General Instructions for Electrical Wiring on page 47

for the wiring/terminal diagram for each option.
Unless otherwise specified, the default is Option 1. The

wiring arrangement is identified on the detector by the

part number (see Model and Types on page 2).

Option 1: Power, RS-485, 0-20mA (Sink), Fault I
Relay (N.C), Alarm Relay, (N.O) (see Figure 6).

Option 2: Power, RS-485, 0-20mA (Source) and

HART protocol, Fault Relay (N.O), Alarm Relay, (N.O),

(N.C).