Single IR Flame Detector User Guide

26 Connecting

the

Detector

8

Check the wires for secure mechanical connection and press them neatly

against the terminal to prevent them from interfering while closing the

back cover (Figure 6).

9

Place and secure the detector’s back cover by screwing the three (3)

socket-head-screws in the Cover Bolts (Figure 3).

2.7.1

Verifying the Detector Wiring

The detector has five output wiring options within the EExde integral

terminal section of the enclosure. There are 12 terminals labeled 1-12.
Table 15 describes the function of each terminal for all the wiring options.
Table 15: Model 40/40R Wiring Options

Wire

Terminal

No.

Option 1

Default

Option 2

Option 3

Option 4

Option 5

1

+24 VDC

+24 VDC

+24 VDC

+24 VDC

+24 VDC

2 0

VDC 0

VDC 0

VDC 0

VDC 0

VDC

3

Manual

BIT

Manual

BIT

Manual

BIT

Manual

BIT

Manual

BIT

4

5

Fault

Relay N.C.

Fault

Relay N.C.

Fault

Relay N.O.

Fault

Relay N.C.

Fault

Relay N.O.

6

Alarm

Relay N.O.

Alarm

Relay N.O.

Alarm

Relay N.O.

Alarm

Relay N.O.

Alarm

Relay N.O.

7

Alarm

Relay C

Alarm

Relay C

Alarm

Relay C

Alarm

Relay C

Alarm

Relay C

8

0-20mA

In

Alarm

Relay N.C.

Alarm

Relay N.C.

Auxiliary

N.O.

Auxiliary

N.O.

9

0-20mA

Out

0-20mA

Out*

0-20mA

Out*

Auxiliary

C

Auxiliary C

10

RS-485+

(1)

RS-485+

(1)

RS-485+

(1)

RS-485+

(1)

RS-485+

(1)

11

RS-485-

(1)

RS-485-

(1)

RS-485-

(1)

RS-485-

(1)

RS-485-

(1)

12

RS-485

GND

RS-485

GND

RS-485

GND

RS-485

GND

RS-485

GND

*Available with the HART protocol.
Notes:
• RS-485 is used for communication network as specified in Appendix C

(Terminals 10, 11, 12) and to connect (in safe area) to PC/Laptop for

configuration/diagnostics.

• Alarm relay:

• N.O. energized contact in wiring options 1, 4, 5.
• N.O. and N.C. energized in options 2 and 3.