General Instructions for Electrical Wiring

47

B Wiring

Instructions

In this appendix…

General Instructions for Electrical Wiring

page 47

Typical Wiring Configurations

page 49

B.1

General Instructions for Electrical Wiring

Follow the instructions detailed in this section for determining the correct

wire gauge to be used for the installation.

1

Use Table 24 to determine the required wire gauge /size for general

wiring, such as relay wiring. Calculate the permitted voltage drop with

respect to load current, wire gauge and length of wires.
Table 24: Maximum DC resistance at 68°F (20ºC) for copper wire

AWG #

mm

2

Ohm per 100 ft. Ohm per 100 m

26 0.12

-

0.15 4.32

14.15

24 0.16

-

0.24 3.42

11.22

22 0.30

-

0.38 1.71

5.60

20 0.51

-

0.61 1.07

3.50

18 0.81

-

0.96 0.67

2.20

16 1.22

-

1.43 0.43

1.40

14 1.94

-

2.28 0.27

0.88

12 3.09

-

3.40 0.17

0.55

10 4.56

-

6.64 0.11

0.35

2

Use Table 25 to select wire gauge for power supply wires. DO NOT

connect any circuit or load to detectors’ supply inputs.
• Select Number of detectors connected in one circuit.
• Select wiring Length per your installation requirements.
• Refer to Power Supply Range for voltage extreme applied.