3 function set-up, 4 heated optics – Spectrex 40/40R - Single IR Flame Detector User Manual
Page 41
TM 40/40R, Rev (4) November 2010
Configuring your Detector
29
2.8.3 Function
Set-up
You can select the desired functions as detailed in Table 16.
Table 16: Functions
Function
Setting
Alarm Latch
•
Yes: Enable Alarm latching.
•
No: Disable Alarm latching (default).
Auxiliary Relay**
•
Yes: Activate Auxiliary Relay at Warning level.
•
No: Activate Auxiliary Relay at Alarm level
(default).
Automatic BIT
•
Yes: Perform Automatic & Manual Bit (default).
•
No: Perform Manual Bit only.
Alarm BIT
•
Yes: Successful Manual Bit activates the Alarm
Relay for approximately 3 seconds (default).
•
No: Successful Manual Bit does not activate the
Alarm Relay.
Auxiliary BIT**
•
Yes: Successful Manual Bit activates the
Auxiliary Relay for approximately 3 seconds
(default).
•
No: Successful Manual Bit does not activate the
Auxiliary Relay.
EOL**
•
Yes: Auxiliary Relay is used as End of Line.
•
No: Auxiliary Relay operates in accordance with
Function 2 and 5 (default).
Note: ** only available in Model 40/40R-4XXXX and 5XXXX
2.8.4 Heated
Optics
The heated optics can be defined as one of the following modes:
• Heated Mode
• OFF: Not operated
• On: Continuously
• AUTO: Per temperature change
In AUTO mode, the default HEAT ON setting is 41°F (5°C). Heating stops
when the temperature is 27°F (15°C) above the start temperature.
You can define the start temperature below which the window will be
heated. The temperature can be defined between 32°F and 122°F (0°C to
50°C).