Spectrex 40/40R - Single IR Flame Detector User Manual

Page 27

background image

TM 40/40R, Rev (4) November 2010

Internal Detector Tests

15

1.6.2.2 Automatic

BIT

The detector automatically performs a BIT every 15 minutes. A successful
BIT sequence does not activate any indicator.
The results of a successful and unsuccessful BIT are listed in Table 8 and

Table 9.
Table 8: Results of a Successful BIT

Output

Result

Fault relay

Wiring options 1, 2, 4: remains CLOSED

Wiring options 3 and 5: remains OPEN

0-20mA output

Wiring option 1, 2, 3: Normal (4 mA)

Power LED

Green, Flashing, 1 Hz On (Normal)

Table 9: Results of an Unsuccessful BIT

Output

Result

Fault relay

Wiring option 1, 2, 4: changes to Open

Wiring option 3 and 5: changes to Closed

0-20mA output

Wiring option 1, 2, 3: BIT Fault (2mA)

Power LED

Yellow, Flashing, 4 Hz

BIT procedure

Performed every 1 minute

1.6.2.3 Manual

BIT

The BIT is manually initiated by momentarily connecting Terminal 3 with

Terminal 2 (or a switch across these terminals in the safe area).
If the BIT is unsuccessful, all outputs will function as described for

Automatic BIT, but the BIT is now automatically executed every 1 minute.

This continues until a successful BIT occurs, when the detector will resume

normal operation.
The results of a successful and unsuccessful Manual BIT are listed in

Table 10 and Table 11.