62

40/40R Optical Flame Detector

E.1.2.1

Conditions for Safe Operating

1

The flame detector shall consist only of the approved hardware and

software modules.

2

The 24V power supply must fulfill the requirements for PELV / SELV of

EN 60950.

3

The automatic BIT (Built-In-Test) must be activated.

4

The set-up parameters must be verified (as described in

Using the 0-20mA Interface for Alerting on page 62, point

1

and in Using

the Alarm Relay Contact for Alerting on page 62, point

1) and the

function of the 40/40 Flame Detector (flame detection, function of the

0-20mA interface, relay functions) must be checked completely.

E.1.2.2

Using the 0-20mA Interface for Alerting

1

The following parameters shall be set:
• AUTOMATIC BIT test = on
• Connected to 0-20mA Terminals

2

The following allowed output current must be supervised with an

accuracy of ± 5%:
• Normal State = 4mA
• Warning State = 16mA
• Alarm State = 20mA

3

The output current must be supervised regarding the over-and under run
of the 0-20mA.

E.1.2.3

Using the Alarm Relay Contact for Alerting

1

The following parameters shall be set:
• AUTOMATIC BIT Test = on
• Connected to N.C contact of Alarm Relay Terminals
• Connected to Fault Relay Terminals

2

The relay contacts (“alarm” – and “faulty relay”) must be protected with
a fuse rated at 0.6 of the nominal specified relay contact current.

3

The maximum contact rating that is allowed per SIL-2 is 30VDC.

4

It is to be considered that the contact of the Alarm Relay opens if there

is a fire alarm.

5

During the forwarding and evaluation of the alarm it must be noted that

the relay contact opens.

6

The alarm relay can be used as low demand only.