beautypg.com

8 configuring your detector – Spectrex 40/40R - Single IR Flame Detector User Manual

Page 39

background image

TM 40/40R, Rev (4) November 2010

Configuring your Detector

27

• 0-20mA is ‘Sink’ in option 1 and ‘Source’ in option 2 and 3.
• 0-20mA 'Source' in options 2 and 3 available with the HART protocol.
• In Wiring Option 1, link Terminals 1 and 8 to change the mA output to

‘Source’.

• The Fault output is N.C. energized SPST relay. The contacts are closed

when the Detector is in its normal operational condition in options 1, 2

and 4, and available as N.O. energized in options 3 and 5.

• The Auxiliary output is N.O. energized (SPST) relay. The Auxiliary Relay

may act in parallel with the ALARM relay to activate another external

device or it may provide a warning signal, depending on the function

configuration.

2.8

Configuring your Detector

You can reprogram the function setup using the RS-485 connection or using
the HART protocol as follows:
Mini Laptop Kit (P/N 777820): The mini laptop, pre-loaded with the

Spectrex host software, enables you to re-configure settings or perform

diagnostics on all 40/40 series flame detectors.

Refer to manual TM777070 for programming instructions when using the
Mini Laptop Kit.

USB RS485 Harness Kit (P/N 794079-5): The USB RS485 Harness Kit

with RS485/USB converter, used with the Spectrex host software,

enables you to connect to any available PC or laptop to re-configure

settings or perform diagnostics on all 40/40 series flame detectors.

Refer to manual TM777050 for programming instructions when using the
USB RS485 Harness Kit.

HART Protocol: Refer to Manual TM 777030 for programming

instructions.

These functions enable you to set:
• Alarm Delay
• Address Setup
• Mode of Operation
• Heated Optics Operation
The factory Default settings listed for each function are:
• Alarm Delay – A
• Alarm Latch – No
• Auxiliary Relay – No
• Automatic BIT – Yes
• Alarm BIT – No
• Auxiliary BIT – No