SharpEye

TM

Single IR Flame Detector User Guide

34

Testing Procedures

To perform Fire Simulator Test:

1

Power up the system and wait up to 60 seconds for the detector to turn

to a normal state. The Power LED turns on.

2

Aim the Spectrex Fire Simulator Model 20/20/312 at the target point of

the detector (Figure 15), in a way that the radiation emitted by it is

facing directly towards the detector. (See Long Range Fire Simulator on
page 55).

3

Press the operation button once. After few seconds, a successful test
shows the results shown in Table 18.

Table 18: Results of Successful Fire Simulator Test

Component

Action

Notes

0-20mA

Turn to 20mA

For a few seconds and then return to

4mA

Alarm Relay

Activated

for a few seconds and then returns to

Normal

Auxiliary Relay

Activated

for a few seconds and then returns to

Normal

Fault Relay

Remains active

during the test

LED Red,

steady

The detector is now ready for operation.