1

1 Introduction

In this chapter…

Overview page

1

Model and Types

page 2

Features and Benefits

page 4

Principles of Operation

page 4

Performance Considerations

page 7

Internal Detector Tests

page 13

1.1 Overview

The 40/40R Single IR Flame Detector detects hydrocarbon-based fuel and

gas fires using advanced flame tools.
All 40/40 series detectors include a heated optical window for improved

performance in icing, snow and condensation conditions.
Detection performance can be easily adapted to all environments,

applications and requirements, by changing the detector’s configuration

parameters. Adjusting these parameters, as well and performing other

maintenance and monitoring tasks, is possible by means of RS485-based

Modbus communication or HART communication (in models with 0-20mA

output).
The detector enclosure is ATEX certified EExd flameproof with an integral,

segregated, rear, EExe terminal compartment (avoiding exposure of the
sensors and electronics to surrounding environment). Hence the combined

approval EExde IIB + H2 T5 (75°C) or T4 (85°C).
The SharpEye 40/40 detectors are designed to operate as a stand-alone unit

directly connected to an alarm system or an automatic fire extinguishing
system. The detector can also be a part of a more complex system, where

many detectors and other devices are integrated through a common control

unit.