beautypg.com

5 product certification – Spectrex 40/40R - Single IR Flame Detector User Manual

Page 18

background image

SharpEye

TM

Single IR Flame Detector User Guide

6

Principles of Operation

1.4.5 Product

Certification

The 40/40R Flame Detectors have the following certifications:
• ATEX, IECEx, page 6
• FM, CSA, page 6
• SIL-2 Approved (TÜV), page 6
• EN54-10, page 6

1.4.5.1 ATEX,

IECEx

The 40/40R Optical Flame Detector is certified to:
• ATEX Ex II 2 GD per SIRA 07ATEX 1149 and IECEx SIR. 07.0085.
• EExde IIB + H

2

:

• T5 Ambient Temp. -55°C to +75°C.
• T4 Ambient Temp. -55°C to +85°C.
This product is suitable to use in hazardous zones 1 and 2 with IIB + H

2

gas

group vapors present.

1.4.5.2 FM,

CSA

The 40/40R Optical Flame Detector is certified to FM and CSA Explosion

Proof per:
• Class I, Division 1, Groups B, C and D, T5 Ta = 85°C.
• Dust Ignition Proof – Class II/III Division 1, Groups E, F and G.
• Ingress Protection – IP67, IP66, NEMA 250 Type 6P.
• For more details see Report Project ID3029553.

1.4.5.3

SIL-2 Approved (TÜV)

The 40/40R Optical Flame Detector is certified to SIL-2 requirement per IEC

61508.4, Chapter 3.5.12.
The alert condition according to SIL-2 can be implemented by:
• Alert signal via 0-20mA current loop.

or

• Alert signal via alarm relay and fault relay.
• For more details and guidelines for configuring, installing, operating and

service – see SIL-2 Features on page 61 and TÜV Report No.

968/EZ348.00/009.

1.4.5.4 EN54-10

The 40/40R Optical Flame Detector is certified to EN54-10 and CPD.
• The detector has been tested and approved per EN54-10 by LPCB

(BRE, UK).