D.1.1 unpacking, D.1.2 operating instructions – Spectrex 40/40R - Single IR Flame Detector User Manual
Page 68
SharpEye
TM
Single IR Flame Detector User Guide
56
Long Range Fire Simulator
D.1.1 Unpacking
Verify that you have received the following contents:
• Delivery form
• Fire Simulator with integral batteries
• Battery charger
• Storage case
D.1.2 Operating
Instructions
Warning: Do not open the Fire Simulator to charge the batteries or for any
other reason in a hazardous area.
Caution: The following test simulates a real fire condition and may activate
the extinguishing system or other alarms. If this is not desired,
disconnect/inhibit them before the test and reconnect after the simulation.
To simulate a fire:
1
Aim the Fire Simulator towards the detector’s Target Point
Figure 15: 40/40R Detector Target Point
2
When testing keep a distance of at least 50 cm (20 inches) from the
detector.
3
Press the operation button once. Fire simulation lasts for 20 seconds.
The detector sends an alarm signal (solid red LED).
4
Wait 20 seconds before repeating the test.
5
Verify that the optical window is clean.
Target Point