Long Range Fire Simulator

D.1.1 Unpacking

Verify that you have received the following contents:
• Delivery form
• Fire Simulator with integral batteries
• Battery charger
• Storage case

D.1.2 Operating

Instructions

Warning: Do not open the Fire Simulator to charge the batteries or for any

other reason in a hazardous area.
Caution: The following test simulates a real fire condition and may activate

the extinguishing system or other alarms. If this is not desired,
disconnect/inhibit them before the test and reconnect after the simulation.

To simulate a fire:

1

Aim the Fire Simulator towards the detector’s Target Point

Figure 15: 40/40R Detector Target Point

2

When testing keep a distance of at least 50 cm (20 inches) from the
detector.

3

Press the operation button once. Fire simulation lasts for 20 seconds.

The detector sends an alarm signal (solid red LED).

4

Wait 20 seconds before repeating the test.

5

Verify that the optical window is clean.

Target Point