beautypg.com

Martel Electronics BetaGauge 3II User Manual

Page 84

background image

5-17

Advanced Display Modes

3.

Press the function key corresponding to Sqrt and
the display screen prompts you for the field
instrument’s expected output signal for a 0% flow.
A sample screen is shown below:

4.

Use the keypad numbers to enter the value of the
expected output milliamp signal when the flow is
equal to 0% (typically 4 for a 4-20 milliamp
output). Press the ENTER key.

5.

The display screen individually prompts you for the
following values:
 expected output milliamp signal when the flow

is equal to 100% (typically 20 for a
4 to 20 milliamp output)

 number equal to the low end flow variable; for

example, if the process was 2 to 300 GPM,
you would enter 2.

 number equal to the high end flow variable; for

example, if the process was 2 to 300 GPM,
you would enter 300.

Repeat step 4 to enter values for each of the above
prompts.

6.

After you have specified all of the values in step 5,
the following display screen appears:

CHx Instr. Out Lo

CHx Ent. Decimals: