Operation – KROHNE PTIFLEX 2200 FOUNDATION FIELDBUS User Manual

Page 65

background image

OPERATION

4

65

OPTIFLEX 2200 C

www.krohne.com

09/2013 - 4002573201 - AD FF OPTIFLEX 2200 R01 en

Alarm State

R

A discrete enumeration which gives an indication of whether

the alert is active and whether it has been reported.

Uninitialized

Setting:

Uninitialized

Clear - reported: Alarm not active and reported

Clear - not reported: Alarm not active and not reported

Active - reported: Alarm active and reported

Active - not reported: Alarm active and not reported

Time Stamp

R

The time when evaluation of the block was started and a

change in alarm/event state was detected that is unreported.

The time stamp value will be maintained constant until alert

confirmation has been received - even if another change of

state occurs.

Uninitialized

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

Subcode

R

An enumeration specifying the cause of the alert to be

reported.

Other

Setting:

Settings see above parameter "BLOCK_ALM", subelement

"Subcode".

Value

R

The value of the associated parameter at the time the alert

was detected.

0

HI_HI_ALM

HI_HI_ALM

HI_HI_ALM

HI_HI_ALM

High High Alarm

High High Alarm

High High Alarm

High High Alarm

Mix

The status for High High Alarm and its associated time stamp. -

Unacknowledged

R/W

A discrete enumeration which is set to "Unacknowledged"

when an alarm occurs, and set to "Acknowledged" by a write

from a human interface device or other entity which can

acknowledge that the alarm/event has been noticed.

Uninitialized

Setting:

Uninitialized / Acknowledged / Unacknowledged

Alarm State

R

A discrete enumeration which gives an indication of whether

the alert is active and whether it has been reported.

Uninitialized

Setting:

Uninitialized

Clear - reported: Alarm not active and reported

Clear - not reported: Alarm not active and not reported

Active - reported: Alarm active and reported

Active - not reported: Alarm active and not reported

Time Stamp

R

The time when evaluation of the block was started and a

change in alarm/event state was detected that is unreported.

The time stamp value will be maintained constant until alert

confirmation has been received - even if another change of

state occurs.

Uninitialized

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

Subcode

R

An enumeration specifying the cause of the alert to be

reported.

Other

Setting:

Settings see above parameter "BLOCK_ALM", subelement

"Subcode".

Value

R

The value of the associated parameter at the time the alert

was detected.

0

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value