Operation – KROHNE PTIFLEX 2200 FOUNDATION FIELDBUS User Manual

Page 40

background image

4

OPERATION

40

OPTIFLEX 2200 C

www.krohne.com

09/2013 - 4002573201 - AD FF OPTIFLEX 2200 R01 en

TRANSDUCER_VALUE

Transducer Value

R

Current value supplied by transducer.

0.0

ENABLE_DISABLE

Simulate En/Disable

RW

The parameter "SW_Simulated" in RB Block must be enabled. Disabled

Setting:

Uninitialized / Disabled / Active

STATUS_OPTS

STATUS_OPTS

STATUS_OPTS

STATUS_OPTS

Status Option

Status Option

Status Option

Status Option

RW

Options which the user may select in the block processing of

status.

Uninitialized

Setting:

Propagate Fault Forward / Uncertain if limited / BAD if

limited / Uncertain if Man.

UPDATE_EVT

UPDATE_EVT

UPDATE_EVT

UPDATE_EVT

Update Event

Update Event

Update Event

Update Event

This alert is generated by any change to the static data.

UNACKNOWLEDGED

Unacknowledged

RW

A discrete enumeration which is set to "Unacknowledged"

when an alarm occurs, and set to "Acknowledged" by a write

from a human interface device or other entity which can

acknowledge that the alarm/event has been noticed.

Uninitialized

Setting:

Uninitialized / Acknowledged / Unacknowledged

UPDATE_STATE

Update State

R

A discrete enumeration which gives an indication of whether

the alert has been reported.

Uninitialized

Setting:

Uninitialized / Reported / Not Reported

TIME_STAMP

Time Stamp

R

The time when evaluation of the block was started and a

change in alarm/event state was detected that is unreported.

The time stamp value will be maintained constant until alert

confirmation has been received - even if another change of

state occurs.

Uninitialized

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

STATIC_REVISION

Static Rev

R

The static revision of the block whose static parameter was

changed and is being reported. It is possible for the present

value of static revision to be greater than this because static

can be changed at any time.

0

RELATIVE_INDEX

Relative Index

R

The OD index of the static parameter whose change caused

this alert, minus the FB starting index. If the update event was

caused by a write to multiple parameters at the same time,

then this attribute will be zero.

0

XD_SCALE

XD_SCALE

XD_SCALE

XD_SCALE

Transducer Scale

Transducer Scale

Transducer Scale

Transducer Scale

RW

The high and low scale values, engineering units code and

number of digits to the right of the decimal point used with the

value obtained from the transducer for a specified channel.

-

EU_100

EU at 100%

RW

The engineering unit value which represents the upper end of

range of the associated block parameter.

100.0

EU_0

EU at 0%

RW

The engineering unit value which represents the lower end of

range of the associated block parameter.

0.0

UNITS_INDEX

Units Index

RW

Device Description units code index for the engineering unit

descriptor for the associated block value.

Depends on the

type, the device is

calibrated for

Units:

Units:

Units:

Units:

m; cm; mm; ft; in; gal; L; ImpGal; m³; bbl; ft³; kg; t; STon; LTon

DECIMAL

Decimal

RW

The number of digits to the right of the decimal point which

should be used by an interface device in displaying the

specified parameter.

0

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value