Technical data, 1 foundation™ fieldbus data – KROHNE PTIFLEX 2200 FOUNDATION FIELDBUS User Manual
Page 5
TECHNICAL DATA
2
5
OPTIFLEX 2200 C
www.krohne.com
09/2013 - 4002573201 - AD FF OPTIFLEX 2200 R01 en
2.1 FOUNDATION™ Fieldbus data
Description
Type
2-wire loop-powered level transmitter; Time Domain Reflectometry (TDR)
Physical layer
FOUNDATION™ fieldbus protocol that agrees with IEC 61158-2 and FISCO model;
galvanically isolated
Communication standard
H1
ITK version
6.1
Link Active Scheduler
Supported
Data blocks
Function blocks
1 x Resource Block (RB)
1 x Level Transducer Block
1 x Display Transducer Block
1 x Diagnose Transducer Block
3 x Analog Input Block (AI)
1 x Proportional Integral Derivate Block (PID)
Execution time
Analog Input Block: 30 ms
Proportional Integral Derivate Block: 40 ms
Minimum cycle time
250 ms
Electrical connections
Device power supply
Not intrinsically safe: 9...32 VDC
Intrinsically safe: 9...24 VDC
Basic current
14 mA
Maximum error current
20.5 mA (= basic current + error current = 14 mA + 6.5 mA)
Error current FDE
Typically 6.5 mA (FDE =Fault Disconnection Electronic)
Polarity sensitivity
No
Minimum cycle time
250 ms
Input and output
Output data
Level, distance, ullage conversion, level conversion
Input data
None