Technical data, 1 foundation™ fieldbus data – KROHNE PTIFLEX 2200 FOUNDATION FIELDBUS User Manual

Page 5

background image

TECHNICAL DATA

2

5

OPTIFLEX 2200 C

www.krohne.com

09/2013 - 4002573201 - AD FF OPTIFLEX 2200 R01 en

2.1 FOUNDATION™ Fieldbus data

Description

Type

2-wire loop-powered level transmitter; Time Domain Reflectometry (TDR)

Physical layer

FOUNDATION™ fieldbus protocol that agrees with IEC 61158-2 and FISCO model;

galvanically isolated

Communication standard

H1

ITK version

6.1

Link Active Scheduler

Supported

Data blocks

Function blocks

1 x Resource Block (RB)

1 x Level Transducer Block

1 x Display Transducer Block

1 x Diagnose Transducer Block

3 x Analog Input Block (AI)

1 x Proportional Integral Derivate Block (PID)

Execution time

Analog Input Block: 30 ms

Proportional Integral Derivate Block: 40 ms

Minimum cycle time

250 ms

Electrical connections

Device power supply

Not intrinsically safe: 9...32 VDC

Intrinsically safe: 9...24 VDC

Basic current

14 mA

Maximum error current

20.5 mA (= basic current + error current = 14 mA + 6.5 mA)

Error current FDE

Typically 6.5 mA (FDE =Fault Disconnection Electronic)

Polarity sensitivity

No

Minimum cycle time

250 ms

Input and output

Output data

Level, distance, ullage conversion, level conversion

Input data

None