Operation, 4 resource block (rb) – KROHNE PTIFLEX 2200 FOUNDATION FIELDBUS User Manual
Page 13
OPERATION
4
13
OPTIFLEX 2200 C
www.krohne.com
09/2013 - 4002573201 - AD FF OPTIFLEX 2200 R01 en
4.4 Resource Block (RB)
The following tables list the Resource Block parameters in alphabetical order.
It describes characteristics of the Fieldbus device (e.g. device name, serial number, etc.) and is
not included in the functional tasks of the signal converter for FF.
The following tables contain short parameter description, factory settings (Initial Value (IV)) and
possible settings.
4.4.1 Foundation Fieldbus parameters for Resource Block
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value
ALERT_KEY
ALERT_KEY
ALERT_KEY
ALERT_KEY
Alert Key
Alert Key
Alert Key
Alert Key
RW
The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
0
Setting:
1...255
BLOCK_ERR
BLOCK_ERR
BLOCK_ERR
BLOCK_ERR
Block Error
Block Error
Block Error
Block Error
R
This parameter reflects the error status associated with the
hardware or software components associated with a block. It
is a bit string, so that multiple errors may be shown.
OOS (Out of
Service)
Setting:
•
Other: Non-specific error active
•
Block Configuration: Error detected in block configuration
•
Link Configuration: Error detected in link configuration
•
Simulation Active: Simulation enabled in this block
•
Local Override: Output tracking of faultstate active
•
Device Fault State: Device faultstate set
•
Device Maintenance: Device needs maintenance soon
•
Input Failure: Process variable has bad status
•
Output Failure: Failure detected in output hardware
•
Memory Failure: Memory error detected
•
Lost Static Data: Static parameters cannot be recovered
•
Lost NV Data: Non-volatile parameters cannot be recovered
•
Readback Check: Failure detected in READBACK
•
Maintenance Needed: Device NEEDS maintenance NOW
•
Power Up: Recovery from power failure
•
Out Of Service: Block actual mode is out of service
MODE_BLK
MODE_BLK
MODE_BLK
MODE_BLK
Block Mode
Block Mode
Block Mode
Block Mode
The actual, target, permitted and normal modes of the block.
-
TARGET
Target
RW
This is the mode requested by the operator. Only one mode
from those allowed by the permitted mode parameter may be
requested.
OOS
Setting:
Auto / OOS
ACTUAL
Actual
R
This is the current mode of the block, which may differ from
the target based on operating conditions. Its value is
calculated as part of block execution.
OOS
Setting:
Auto / OOS
PERMITTED
Permitted
RW
Defines the modes which are allowed for an instance of the
block. The permitted mode is configured based on application
requirement.
Auto
OOS
Setting:
Auto / OOS