Operation – KROHNE PTIFLEX 2200 FOUNDATION FIELDBUS User Manual

Page 47

background image

OPERATION

4

47

OPTIFLEX 2200 C

www.krohne.com

09/2013 - 4002573201 - AD FF OPTIFLEX 2200 R01 en

PROBE_END_THRESHOLD

PROBE_END_THRESHOLD

PROBE_END_THRESHOLD

PROBE_END_THRESHOLD

Probe end threshold

Probe end threshold

Probe end threshold

Probe end threshold

RW

For measurement in TBF mode. If it is difficult to identify the

probe end signal (for example: too many parasite signals) you

can increase the threshold of the signal. A threshold of 1000 is

equivalent to the amplitude of the measurement pulse. A

threshold of 100 is equivalent to 10% of the amplitude of the

measurement pulse.

PROBE_LENGTH

PROBE_LENGTH

PROBE_LENGTH

PROBE_LENGTH

Probe Length

Probe Length

Probe Length

Probe Length

RW

The distance from the flange face / thread stop of the device

down to the bottom end of the probe (including counterweight

for cable versions). If probe length has been modified, enter

the new value here.

Setting:

0…40000

SECONDARY_VALUE

SECONDARY_VALUE

SECONDARY_VALUE

SECONDARY_VALUE

electronic temperature

electronic temperature

electronic temperature

electronic temperature

The Electronic temperature.

STATUS

Status

R

Digital transducers, unlike their analog versions, can detect

faults that make the measurement bad or prevent the

actuator from responding. This additional, valuable

information will be passed along with each transmission of a

data value in the form of a status attribute.

-0

VALUE

Value

R

A numerical quantity entered by a user or calculated by the

algorithm.

SECONDARY_VALUE_UNIT

SECONDARY_VALUE_UNIT

SECONDARY_VALUE_UNIT

SECONDARY_VALUE_UNIT

electronic temperature unit

electronic temperature unit

electronic temperature unit

electronic temperature unit

RW

The engineering units to be used with SECONDARY_VALUE

(electronic temperature).

°C

Setting:

K; °C; °F; °R

SENSOR_CAL_DATE

SENSOR_CAL_DATE

SENSOR_CAL_DATE

SENSOR_CAL_DATE

Sensor Calibration Date

Sensor Calibration Date

Sensor Calibration Date

Sensor Calibration Date

R

The date of the last sensor calibration.

-

SENSOR_CAL_LOC

SENSOR_CAL_LOC

SENSOR_CAL_LOC

SENSOR_CAL_LOC

Sensor Calibration Location

Sensor Calibration Location

Sensor Calibration Location

Sensor Calibration Location

R

The last physical location at which the sensor was calibrated.

(ex. Acme Labs)

-

SENSOR_CAL_METHOD

SENSOR_CAL_METHOD

SENSOR_CAL_METHOD

SENSOR_CAL_METHOD

Sensor Calibration method

Sensor Calibration method

Sensor Calibration method

Sensor Calibration method

R

The method of last sensor calibration. It could be one of the

several standard calibration methods defined by ISO or some

other method.

factory trim

standard

calibration

SENSOR_RANGE

SENSOR_RANGE

SENSOR_RANGE

SENSOR_RANGE

Sensor Range

Sensor Range

Sensor Range

Sensor Range

The High and Low range limit values, the engineering units

code and the number of digits to the right of the decimal point

for the sensor.

EU_100

max value

R

The engineering unit value which represents the upper end of

range of the associated block parameter.

EU_0

min value

R

The engineering unit value which represents the lower end of

range of the associated block parameter.

UNITS_INDEX

Units Index

R

Device Description units code index for the engineering unit

descriptor for the associated block value.

DECIMAL

Decimal

R

The number of digits to the right of the decimal point which

should be used by an interface device in displaying the

specified parameter.

2

SENSOR_SN

SENSOR_SN

SENSOR_SN

SENSOR_SN

Sensor Serial Number

Sensor Serial Number

Sensor Serial Number

Sensor Serial Number

R

The sensor serial number.

SENSOR_TYPE

SENSOR_TYPE

SENSOR_TYPE

SENSOR_TYPE

Sensor Type

Sensor Type

Sensor Type

Sensor Type

R

The type of sensor.

Level

SENSOR_CAL_WHO

SENSOR_CAL_WHO

SENSOR_CAL_WHO

SENSOR_CAL_WHO

Sensor Calibration Who

Sensor Calibration Who

Sensor Calibration Who

Sensor Calibration Who

R

The name of the person responsible for the last sensor

calibration.

TANK_HEIGHT

TANK_HEIGHT

TANK_HEIGHT

TANK_HEIGHT

Tank Height

Tank Height

Tank Height

Tank Height

RW

The distance from the tank connecting flange face/thread stop

down to the tank bottom.

Setting:

0…100000

Parameter

Parameter

Parameter

Parameter
DD name

Access Description and settings

Initial Value