OPERATION

32

OPTIFLEX 2200 C

www.krohne.com

09/2013 - 4002573201 - AD FF OPTIFLEX 2200 R01 en

FD_SIMULATE

FD_SIMULATE

FD_SIMULATE

FD_SIMULATE

Field Diagnostic

Field Diagnostic

Field Diagnostic

Field Diagnostic

Simulate

Simulate

Simulate

Simulate

Used as the field diagnostic condition when the simulation is

enabled.

DIAGNOSTIC_

SIMULATE_VALUE

Diagnostic Simulate

Value

RW

Allows the conditions to be manually supplied when simuation is

enabled. The simulate jumper is required for simulation to be

enabled.

Uninitialized

Setting:

(00) Check Function

(01) Cond01

(02) Cond02

(03) Cond03

(04) Cond04

(05) Cond05

(06) Snapshot invalid

(07) Audio Signal Offset outside Range

(08) Reference Position outside Range

(09) Pulse Flange Lost

(10) No Probe detected

(11) Reference Lost Error

(12) Oscillator Frequency failure

(13) Temperature Above +75°C

(14) Temperature Below -35°C

(15) Overfill Warning

(16) Level Lost warning

(17) Temperature out of range (warning)

(18) Local operation

(19) Overfill Error

(20) Level lost error

(21) Temperature out of range Error

(22) Converter Voltage Error

(23) Converter ROM Error

(24) Converter RAM Error

(25) Converter EEPROM Error

(26) Sensor not compatible

(27) Internal Communication Error

(28) Sensor Voltage Error

(29) Sensor ROM Error

(30) Sensor RAM Error

(31) Sensor EEPROM Error

Parameter

Parameter

Parameter

Parameter
DD name

Access Description and settings

Initial Value