Operation – KROHNE PTIFLEX 2200 FOUNDATION FIELDBUS User Manual
Page 38
4
OPERATION
38
OPTIFLEX 2200 C
www.krohne.com
09/2013 - 4002573201 - AD FF OPTIFLEX 2200 R01 en
IO_OPTS
IO_OPTS
IO_OPTS
IO_OPTS
IO Options
IO Options
IO Options
IO Options
(IO = Input/Output)
(IO = Input/Output)
(IO = Input/Output)
(IO = Input/Output)
RW
Options which the user may select to alter input and output
block processing.
Uninitialized
Setting:
Low Cutoff / Units Conversion
L_TYPE
L_TYPE
L_TYPE
L_TYPE
Linearization Type
Linearization Type
Linearization Type
Linearization Type
RW
Determines if the values passed by the TB to the AI block may
be used directly (Direct) or if the value is in different units and
must be converted linearly (Indirect) , or with square root (Ind
Sqr Root), using the input range defined for the transducer
and the associated output range.
Uninitialized
Setting:
Uninitialized / Direct / Indirect / Ind Sqr Root
LO_ALM
LO_ALM
LO_ALM
LO_ALM
Low Alarm
Low Alarm
Low Alarm
Low Alarm
The status for Low Alarm and its associated time stamp.
For settings of the 5 sub-elements, refer to the
"Unacknowledged", "Alarm State", "Time Stamp", "Subcode"
and "Value" items that follow.
-
LO_LO_ALM
LO_LO_ALM
LO_LO_ALM
LO_LO_ALM
Low Low Alarm
Low Low Alarm
Low Low Alarm
Low Low Alarm
The status for Low Low Alarm and its associated time stamp.
For settings of the 5 sub-elements, refer to the
"Unacknowledged", "Alarm State", "Time Stamp", "Subcode"
and "Value" items that follow.
-
Settings of 5 sub-elements for the parameters "Low Alarm" and "Low Low Alarm":
UNACKNOWLEDGED
Unacknowledged
RW
Setting:
Uninitialized / Acknowledged / Unacknowledged
Uninitialized
ALARM_STATE
Alarm State
R
Setting:
Uninitialized / Clear - reported / Clear - not reported / Active -
reported / Active - not reported
Uninitialized
TIME_STAMP
Time Stamp
R
Setting:
MM / DD / YY (Month / Day / Year)
HH:MM:SS (Hour:Minute:Second)
Uninitialized
SUB_CODE
Subcode
R
Setting:
Other/ Block Configuration / Link Configuration / Simulation
Active / Local Override / Device Fault State / Device
Maintenance / Input Failure / Output Failure / Memory
Failure / Lost Static Data / Lost NV Data / Readback Check /
Maintenance Needed / Power Up / Out Of Service
Other
VALUE
Float Value
R
A numerical quantity entered by a user or calculated by the
algorithm.
0.0
LO_LIM
LO_LIM
LO_LIM
LO_LIM
Low Limit
Low Limit
Low Limit
Low Limit
R
The setting for Low Alarm in engineering units.
For the setting range, refer to the " x_y_LIM" item that
follows.
(-NaN)
LO_LO_LIM
LO_LO_LIM
LO_LO_LIM
LO_LO_LIM
Low Low Limit
Low Low Limit
Low Low Limit
Low Low Limit
RW
The setting for Low Low Alarm in engineering units.
For the setting range, refer to the " x_y_LIM" item that
follows.
(-NaN)
LO_PRI
LO_PRI
LO_PRI
LO_PRI
Low Priority
Low Priority
Low Priority
Low Priority
RW
Priority of the Low Alarm.
For the setting range, refer to the " x_y_PRI" item that follows.
0
LO_LO_PRI
LO_LO_PRI
LO_LO_PRI
LO_LO_PRI
Low Low Priority
Low Low Priority
Low Low Priority
Low Low Priority
RW
Priority of the Low Low Alarm.
For the setting range, refer to the " x_y_PRI" item that follows.
0
Setting range for the parameters
"Low Low Limit" and "Low Limit":
x_y_LIM
x_y_Limit
-3.39 E38…+3.39 E38 / - INF (- infinite) / + INF (+ infinite)
Setting range for the parameters
"Low Low Priority" and "Low
Priority":
x_y_PRI
x_y_Priority
Setting:
0...15
0
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value