Operation – KROHNE PTIFLEX 2200 FOUNDATION FIELDBUS User Manual
Page 25
OPERATION
4
25
OPTIFLEX 2200 C
www.krohne.com
09/2013 - 4002573201 - AD FF OPTIFLEX 2200 R01 en
FD_FAIL_MASK
FD_FAIL_MASK
FD_FAIL_MASK
FD_FAIL_MASK
Fail Mask
Fail Mask
Fail Mask
Fail Mask
RW
This parameter allows the user to suppress any single or multiple
conditions that are active, in this category, from being broadcast to
the host through the alarm parameter.
(0)-(31)
masked
Setting:
•
(00) Check Function
•
(01) Cond01
•
(02) Cond02
•
(03) Cond03
•
(04) Cond04
•
(05) Cond05
•
(06) Snapshot invalid disabled
•
(07) Audio Signal Offset outside Range disabled
•
(08) Reference Position outside Range disabled
•
(09) Pulse Flange Lost disabled
•
(10) No Probe detected
•
(11) Reference Lost Error
•
(12) Oscillator Frequency failure disabled
•
(13) Temperature Above +75°C disabled
•
(14) Temperature Below -35°C disabled
•
(15) Overfill Warning disabled
•
(16) Level Lost warning disabled
•
(17) Temperature out of range (warning) disabled
•
(18) Local operation disabled
•
(19) Overfill Error disabled
•
(20) Level lost error disabled
•
(21) Temperature out of range Error disabled
•
(22) Converter Voltage Error disabled
•
(23) Converter ROM Error disabled
•
(24) Converter RAM Error disabled
•
(25) Converter EEPROM Error disabled
•
(26) Sensor not compatible disabled
•
(27) Internal Communication Error disabled
•
(28) Sensor Voltage Error disabled
•
(29) Sensor ROM Error disabled
•
(30) Sensor RAM Error disabled
•
(31) Sensor EEPROM Error disabled
FD_FAIL_PRI
FD_FAIL_PRI
FD_FAIL_PRI
FD_FAIL_PRI
Fail Priority
Fail Priority
Fail Priority
Fail Priority
RW
This parameter allows the user to specify the priority of this alarm
category.
0
Setting:
0...15
FD_MAINT_ACTIVE
FD_MAINT_ACTIVE
FD_MAINT_ACTIVE
FD_MAINT_ACTIVE
Maintenance Active
Maintenance Active
Maintenance Active
Maintenance Active
R
This parameter reflects the error conditions that are being detected
as active as selected for the "Maintenance" category. It is a bit string,
so that multiple conditions may be shown.
FD_MAINT_ALM
FD_MAINT_ALM
FD_MAINT_ALM
FD_MAINT_ALM
Fail Maintenance
Fail Maintenance
Fail Maintenance
Fail Maintenance
Alarm
Alarm
Alarm
Alarm
This parameter is used primarily to broadcast a change in the
associated active conditions, which are not masked, for this alarm
category to a Host System.
UNACKNOWLEDGED
Unacknowledged
RW
A discrete enumeration which is set to "Unacknowledged" when an
alarm occurs, and set to "Acknowledged" by a write from a human
interface device or other entity which can acknowledge that the
alarm/event has been noticed.
Uninitialized
Setting:
Uninitialized / Acknowledged / Unacknowledged
Parameter
Parameter
Parameter
Parameter
DD name
Access Description and settings
Initial Value