Operation – KROHNE PTIFLEX 2200 FOUNDATION FIELDBUS User Manual
Page 31
OPERATION
4
31
OPTIFLEX 2200 C
www.krohne.com
09/2013 - 4002573201 - AD FF OPTIFLEX 2200 R01 en
FD_RECOMMEN_ACT
FD_RECOMMEN_ACT
FD_RECOMMEN_ACT
FD_RECOMMEN_ACT
Recommended Action
Recommended Action
Recommended Action
Recommended Action
R
This parameter is a device enumerated summarization of the most
severe condition or conditions detected. The DD help should
describe by enumerated action, what should be done to alleviate the
condition or conditions.
Uninitialized
Setting:
•
Uninitialized
•
The device operates satisfactorily. No action is required.
•
The "Simulate" jumper is installed. Remove the jumper to go back
to normal operation.
•
The Transducer Block into AUTO mode. Set Transducer Block into
AUTO mode.
•
Make sure that the HART Slave operates satisfactorily
•
Contact the supplier
•
Replace the electronics module or contact the supplier
•
Check the power supply at the device terminals. If the voltage is
correct, contact the supplier.
•
Measure the voltage at the device terminals. Make sure that the
internal cable is connected between the front end and the back
end. For remote configuration, make sure that that the electrical
wires are connected to the terminals. If necessary, contact the
supplier.
•
Temperature is above +85°C / +185°F or below -45°C / -49°F.
Process temperature or ambient temperature is above the
maximum limit or below the minimum limit. Action: Measure the
device temperature.
•
Firmware incompatibility. Contact the supplier.
•
Replace the electronics module or contact the supplier
•
Measure the level signal amplitude of the device. Configure the
device. If necessary, contact the supplier.
•
The level signal is in the blocking distance. Action: Lower the level
until it is below the blocking distance.
•
Make sure that the probe is attached to the process connection. If
necessary, contact the supplier.
•
Risk of device failure. Replace the electronics module or contact
the supplier.
•
Do a check of the device, the tank and the process. Action: do a
new snapshot of the tank contents. Use the snapshot to filter
parasitic signals. If necessary, contact the supplier.
•
Risk of device failure. Replace the electronics module or contact
the supplier.
•
Risk of device failure. Replace the electronics module or contact
the supplier.
•
The electronics block is near to its minimum or maximum
operating temperature. Action: Measure the device temperature.
•
The electronics block is near to its minimum or maximum
operating temperature. Action: Measure the device temperature.
•
Temperature is above +85°C / +185°F or below -45°C / -49°F.
Process temperature or ambient temperature is above the
maximum limit or below the minimum limit. Action: Measure the
device temperature.
•
Check the level signal amplitude of the device. Configure the
device. If necessary, contact the supplier.Recommended action
for Condition 27
•
The level signal is in the blocking distance. Action: Lower the level
until it is below the blocking distance.
•
The device is in configuration mode after a user used the local
display to enter a menu. Action: Use the local display to go back to
normal mode.
•
Unknown Alarm Event appeared
Parameter
Parameter
Parameter
Parameter
DD name
Access Description and settings
Initial Value