OPERATION
4
51
OPTIFLEX 2200 C
www.krohne.com
09/2013 - 4002573201 - AD FF OPTIFLEX 2200 R01 en
UPDATE_STATE
Update State
R
A discrete enumeration which gives an indication of whether
the alert has been reported.
Uninitialized
Setting:
Uninitialized / Update reported / Update not reported
TIME_STAMP
Time Stamp
R
The time when evaluation of the block was started and a
change in alarm/event state was detected that is unreported.
The time stamp value will be maintained constant until alert
confirmation has been received - even if another change of
state occurs.
Uninitialized
Setting:
MM / DD / YY (Month / Day / Year)
HH:MM:SS (Hour:Minute:Second)
STATIC_REVISION
Static Rev
R
The static revision of the block whose static parameter was
changed and is being reported. It is possible for the present
value of static revision to be greater than this because static
can be changed at any time.
0
Setting:
0…65535
RELATIVE_INDEX
Relative Index
R
The OD index of the static parameter whose change caused
this alert, minus the FB starting index. If the update event was
caused by a write to multiple parameters at the same time,
then this attribute will be zero.
0
Setting:
0…65535
COLLECTION_
COLLECTION_
COLLECTION_
COLLECTION_
DIRECTORY
DIRECTORY
DIRECTORY
DIRECTORY
Collection Directory
Collection Directory
Collection Directory
Collection Directory
A directory that specifies the number, starting indices and DD
Item IDs of the data collections in each transducer within a
Transducer Block.
-
DISPLAY_SETTING
DISPLAY_SETTING
DISPLAY_SETTING
DISPLAY_SETTING
Display Setting
Display Setting
Display Setting
Display Setting
Display Setting
LANGUAGE
Display language
R
Display language of the device display
Setting:
English / German / French / Italian / Spanish / Portuguese /
Japanese / Chinese / Russian
LENGTH_UNIT
Display length unit
R
Length unit for level/distance to be shown on the device
display
Setting:
m; cm; mm; in; ft
CONVERSION_UNIT
R
Length/volume/mass conversion unit for the conversion table
and to be shown on the device display
Setting:
m3; liter; US gal; GB gal; ft3; barrel; kg; metric ton; GB ton;
US ton; m; cm; mm; inch; feet; ft3/h; m3/h
SETTING_SEL
SETTING_SEL
SETTING_SEL
SETTING_SEL
Setting selector
Setting selector
Setting selector
Setting selector
RW
Parameter to select predefined display setting
Setting:
None / Setting 1 / Setting 2
SETTING_1
SETTING_1
SETTING_1
SETTING_1
Display setting 1
Display setting 1
Display setting 1
Display setting 1
Display setting 1
SET_LANGUAGE
Display language
RW
Display language of the device display
English / German / French / Italian / Spanish / Portuguese /
Japanese / Chinese / Russian
SET_LENGTH_UNIT
Display length unit
RW
Length unit for level/distance to be shown on the device
display
Setting:
m; cm; mm; in; ft
Parameter
Parameter
Parameter
Parameter
DD name
Access Description and settings
Initial Value