Operation – KROHNE UFM 530 HT EN User Manual

Page 44

background image

6

OPERATION

44

UFM 530 HT

www.krohne.com

12/2013 - 4002393201- HB UFM 530 HT R02 en

3.05.00, PULSE OUTP (Pulse output)

3.05.01

FUNCTION

Function of pulse output with the following options:

1) OFF: switched off, contact closed.

2) ACT FLOW: proportional with the actual volume flow.

3) CORR FLOW: proportional with the corrected volume flow.

4) F/R IND: forward/reverse flow indication. Contact closed for

forward flow, contact open for reverse flow .

5) VOS: proportinal with the velocity of sound (range defined in

function 3.01.11 and 3.01.12).

6) DIG OUTPUT: digital output.

7) BATCH OUTP: batch output indication, only available for the batch-

version. Contact closes at start of the batch and opens when the

batch is reached.

8) GAIN: gain of sensor amplifier, proportional with the signal level.

Range: 0...100 dBV.

9) AN INP 1: proportional with the signal on analog input 1, only

available for the converter functions CORR T and CORR T+P.

11) AN INP 2: proportional with the signal on analog input 2, only

available for the converter functions CORR T and CORR T+P.

3.05.02

DIRECTION

Direction of pulse output, only availabe when ACT FLOW or

CORR FLOW is selected in function 3.05.01.

1) FORWARD: the pulse output will only be active when the flow is in

the forward flow direction as defined in function 3.01.10.

2) BOTH: the pulse output will be active in both flow directions

(forward and reverse), indicating both in the same range.

3.05.03

DIG OUTPUT

Function of digital output, only available when DIG OUTPUT is

selected in function 3.05.01. The pulse output now acts as a digital

output and can be programmed for the following functions:

1) PATH ERR: measuring path error indication (contact open).

2) TOTAL ERR: totalizer error indication (contact open).

3) ALL ERR: indication of all errors (contact open).

4) AN INP ERR: analog input error indication (contact open).

5) OVERRANGE: overrange indication (contact open).

6) TRIP POINT: status output trips if actual flow (Q) goes over a set

limit (an hysteresis is build in). Set points can be set using function

3.05.04 and 3.05.05.

3.05.04

TRIP PNT 1

First trip point.

Range: 0...120% of Q

100%

.

3.05.05

TRIP PNT 2

Second trip point.

Range: 0...120% of Q

100%

.

3.05.06

TIME CONST

Time constant of pulse output (Note: the time constant setting only

applies to actual flow and corrected flow!):

1) 25 ms (lowest value).

2) MASTER TC: time constant has the value set in function 3.01.04.