6

41

UFM 530 HT

www.krohne.com

12/2013 - 4002393201- HB UFM 530 HT R02 en

3.02.13

BATCH VOL

Batch volume total size and units.

Availabe units: m

3

, Liter, US-Gallon, Barrel or user definable unit.

Range: 0.025...100000 m

3

.

3.03.00, DISPLAY.

3.03.01

DISP FLOW

Display of flow. Available options:

1) RATE: full-scale units (flow is shown with the unit as set in function

3.01.01).

2) PERCENT: flow is shown as a percentage (0...100%) of the full

scale value.

3) NO DISPLAY: no flow is shown.

3.03.02

FUNCT TOT

Function of totalizer. Two totalizers (counters) are available. The

totalizer values are incremented and stored once a second. The

following settings are available:

1) ACT FLOW: actual flow units, used for counting the total volume in

the totalizer (for each direction one totalizer is available, the sum of

the two can also be displayed).

2) CORR FLOW: the corrected flow is used for counting the total

volume in the totalizers.

3) POS BOTH: both the actual and the corrected flow are used for

counting the total volume in the totalizers. Note: both are only

counted in the positive direction!

3.03.03

DISP TOTAL

Display of totalizer. A totalizer can be selected here for displaying:

1) TOTAL OFF: both totalizers are switched off, counting stops.

2) FORWARD: forward volume units.

3) REVERSE: reverse volume units.

4) BOTH: both totalizers, alternating.

5) SUM: sum of both totalizers.

6) BOTH + SUM: both totalizers und their sums show alternating.

7) NO DISPLAY: totalizers are not displayed but totalizers count.

3.03.04

TOTAL VOL

Unit for volume totalizer. Note: the maximal value of the totalizer is
99999999 x 10 m

3

and will roll over to 0 at overrun!

Available units: X10 m

3

, US-Gallon, m

3

, barrel, liter.

3.03.05

TOTAL ENER

Unit for the heat energy totalizer. Note: the maximal value of the

totalizer is 99999999 x 10 GJ and will roll over to 0 at overrun!

Available units: X10 GJ, GJ, MJ, GCal., MCal.

3.03.06

VOS

Unit for velocity of sound. Available options:

1) NO DISPLAY: no display of the velocity of sound.

2) m/s, feet/s.

3.03.07

CYCL DISP

If more than one measured value are to be displayed (e.g. flow rate

and totalizer), each value can be selected manually by pressing the

↑ key, or the values can be alternately displayed each five seconds by

turning the cyclic display function on.

3.03.08

ERROR MSG

Display error messages

No. of menu

Display text

Setting/description and functions