KEPCO BOP 1KW-MG Operator Manual, Firmware Ver.2.38 to 2.47 User Manual
Page 29
BOP HIPWR 080709
1-9
MISCELLANEOUS FEATURES (Continued)
Power-up Settings
Mode
Voltage (default) or Current
Main Channel
Reference Type
Internal (default), External or External
Reference Level (Gain Mode)
Protection Limit Channel
Reference type
Internal (default), External
or Lesser Limit
Applies to Limit channel
Protection Limit
Levels
(Internal)
EO
MIN
or IO
MIN
to
1.01 EO
NOM
or IO
NOM
Voltage (Volts) for Current mode,
Current (Amperes) for Voltage mode
Output status
On (default) or Off
Password
Types
Main, Admin1, Admin2
Factory defaults: Main: DEFAULT,
Admin1: A, Admin2: KEPCO
Protection Choices Unprotected, Main, Admin1, Admin2 Password menu always protected by Admin2
Items Protected Interface, max/min , Load type, Test,
Calibration, Power-up, Keypad @
local, Keypad lockout at power-up,
Save Display Chg
(See Figure 3-5 for defaults)
Multiple unit configurations are protected by
Admin2 password.
Save Display Chg choice is Enable or Dis-
able; when set to Disable, prevents changes
made to the display settings from being saved
for power up.
Series, Parallel, Series x Parallel configura-
tions of identical units
Single, Parallel, Series, 2 X 2, 3 X 2 2 X 2 is two parallel branches of two series-
connected identical units.
3 X 2 is two parallel branches of three series-
connected identical units.
GENERAL (ENVIRONMENTAL) CHARACTERISTICS
Temperature
operating
0 to +50 deg C
Full rated load
storage
-20 to +85 deg C
Cooling
Two internal fans
exhaust to the rear
Humidity
0 to 95% RH
non-condensing
Shock
20g. 11msec ±50% half sine
non-operating
Vibration
5-10HZ:
10mm double amplitude
3 axes, non-operating
10-55HZ:
2g
3 axes, non-operating
Altitude
sea level to 10,000 feet
Safety Certification
a-c power
UL 3101-1 and EN 6101-1
Pending
TABLE 1-2. BOP GENERAL SPECIFICATIONS (Continued)
SPECIFICATION
RATING/DESCRIPTION
RATING/DESCRIPTION