3 device management software’s, Device management software’s, Operation – INOR IPAQ R520X User Manual
Page 32

5
OPERATION
C520/C520X / R520/R520X
09/2010 • 86B5200001
www.inor.com
32
5.3.2 Configuration of the 520 series transmitters with handheld communicators FC 375/FC475
The Field communicators FC375/FC475 are handheld communicators from Emerson Process
Management for configuring HART and Foundation Fieldbus devices. To be able to configure the
transmitters with the FC 375/FC475 you need a Device Description (DD) file. The device driver is
possible to download from our website www.inor.com.
The transmitter DD has to be installed on the FC 375/FC475, otherwise the user will work with
the transmitter as generic device loosing opportunity to control all features of the transmitter.
For installing the DD on the FC 375/FC475 the “Easy Upgrade Programming Utility” is needed
and the FC375/FC475 must have a system card with “Easy Upgrade” option (see details in the
“375/475 Field Communicator User’s Manual”).
The transmitter DD for FC375/FC475 can also be downloaded from our website. For information
about installing, follow the instructions in the attached "readme.txt" file.
For proper connection of transmitters with the handheld communicator - see the Figures 7 and
13 for connection of the C520/R520 transmitters and figures 8 and 14 for connection of the
C520X/R520X transmitters.
5.3.3 Device management software’s
The 520 series transmitters can be configured via PC software’s such as AMS Device Manager
or Simatic PDM.
The AMS Device Manager is a PC application from Emerson Process Management for
configuring and managing HART and Foundation Fieldbus devices. For adaptation to different
devices AMS Device Manager uses Device Descriptions (DD).
The C520/C520X / R520/R520X Device Description has to be installed on the AMS System, and a
so called “Installation Kit C520/R520 HART AMS” is needed (available as download on the
internet).
For installing of the DD with the Installation Kit refer to the “AMS Intelligent Device Manager
Books Online" section "Basic AMS Functionality / Device Configurations / Installing Device
Types / Procedures / Install device types from media”. Please read also the “readme.txt”, which
is also contained in the Installation Kit.
The “Installation Kit C520/R520 HART AMS” can also be downloaded from our website
www.inor.com. For information about installing, follow the instructions in the attached
"readme.txt" file.
AMS supports the EDDL Process Variables Root Menu, the Diagnostic Root Menu and the Device
Root Menu for online access to the device.
The Simatic PDM is a PC application from Siemens for configuring HART and PROFIBUS
devices. For adaptation to different devices Simatic PDM uses Device Descriptions (DD).
The C520/C520X / R520/R520X Device Description has to be installed on the PDM System, and a
so called “Device Install C520/R520 HART PDM” is needed (available as download on the
internet).